York R-410A ZH/ZJ/ZR Series Manuel D’Utilisation

Page de 206
528150-YTG-G-1210
44
Johnson Controls Unitary Products
115°F
125°F
1875
77
96.7
8.4
32.9
30.3
22.4
-
-
-
89.9
9.0
27.0
24.2
19.6
-
-
-
72
86.3
8.2
51.1
43.3
35.4
27.5
-
-
79.5
8.8
48.1
40.3
32.5
24.8
-
-
67
75.9
8.0
69.4
56.2
48.4
40.5
32.6
-
69.1
8.5
69.1
53.3
45.5
37.8
30.0
-
62
75.3
7.9
75.3
74.0
59.3
51.5
43.6
35.7
72.2
8.4
72.2
72.2
56.5
48.7
40.9
33.2
2250
77
94.8
8.4
42.0
33.1
24.2
-
-
-
86.1
9.1
38.7
29.7
20.9
-
-
-
72
84.6
8.2
56.0
47.1
38.2
29.3
-
-
76.1
8.8
52.4
43.7
34.9
26.1
-
-
67
74.4
8.1
70.0
61.1
52.2
43.3
34.4
-
66.1
8.6
66.1
57.6
48.8
40.1
31.3
-
62
73.8
7.9
73.8
73.0
64.1
55.2
46.3
37.4
69.3
8.4
69.3
69.3
60.6
51.8
43.1
34.3
57
75.0
7.9
75.0
73.8
64.9
56.0
47.1
38.2
70.1
8.5
70.1
68.9
60.1
51.3
42.6
33.8
2625
77
92.9
8.5
51.1
35.9
26.0
-
-
-
82.3
9.1
50.5
35.2
22.3
-
-
-
72
82.9
8.3
60.9
51.0
41.0
31.1
-
-
72.7
8.9
56.8
47.0
37.2
27.5
-
-
67
72.9
8.1
70.7
66.0
56.1
46.2
36.2
-
63.1
8.6
63.1
61.9
52.1
42.4
32.6
-
62
72.3
8.0
72.3
71.9
68.8
58.9
48.9
39.0
66.4
8.5
66.4
66.4
64.7
54.9
45.2
35.4
57
73.5
8.0
73.5
72.9
69.7
59.8
49.8
39.9
67.1
8.5
67.1
66.5
64.2
54.4
44.6
34.8
3000
77
91.0
8.5
60.2
38.7
27.8
-
-
-
78.5
9.2
62.2
40.6
23.7
-
-
-
72
81.2
8.3
65.8
54.8
43.9
32.9
-
-
69.3
8.9
61.2
50.4
39.6
28.8
-
-
67
71.4
8.2
71.4
70.9
60.0
49.0
38.0
-
60.1
8.7
60.1
60.1
55.5
44.7
33.9
-
62
70.8
8.0
70.8
70.8
73.5
62.6
51.6
40.6
63.5
8.5
63.5
63.5
63.5
58.1
47.3
36.5
57
72.0
8.0
72.0
72.0
74.5
63.5
52.5
41.6
64.1
8.6
64.1
64.1
64.1
57.5
46.7
35.9
3375
72
86.1
8.4
71.9
59.9
47.8
35.7
-
-
75.0
9.0
67.2
55.3
43.5
31.7
-
-
67
75.7
8.2
75.7
75.5
65.3
53.3
41.2
-
65.1
8.7
65.1
65.1
60.9
49.1
37.2
-
62
75.1
8.1
75.1
75.1
76.5
64.4
52.3
40.3
68.6
8.6
68.6
68.6
68.6
59.4
47.5
35.7
57
76.4
8.1
76.4
76.4
77.6
65.5
53.5
41.4
69.3
8.6
69.3
69.3
69.3
59.5
47.6
35.8
3750
72
91.0
8.4
78.0
64.9
51.7
38.5
-
-
80.7
9.0
73.2
60.3
47.4
34.5
-
-
67
80.1
8.2
80.1
80.1
70.7
57.5
44.4
-
70.1
8.8
70.1
70.1
66.3
53.4
40.5
-
62
79.4
8.1
79.4
79.4
79.4
66.2
53.1
39.9
73.6
8.6
73.6
73.6
73.6
60.7
47.8
34.9
57
80.7
8.1
80.7
80.7
80.7
67.6
54.4
41.2
74.4
8.6
74.4
74.4
74.4
61.5
48.6
35.7
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower 
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZH090 (7.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65