System Sensor 2151 Manuel D’Utilisation

Page de 4
D100-04-00
1
I56-581-07R
2151 Low Profile
Photoelectronic Plug-in 
Smoke Detector
INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Before Installing 
Please  thoroughly  read  the  System  Sensor  manual  A05-
1003,  Applications  Guide  for  System  Smoke  Detectors,
which  provides  detailed  information  on  detector  spacing,
placement, zoning, wiring, and special applications. Copies
of this manual are available from System Sensor.
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT:  The  detector  used  with  this  base  must  be
tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.
General Description
The 2151 low-profile photoelectronic detector uses a state-
of-the-art optical sensing chamber. This detector is designed
to provide open area protection and to be used with com-
patible UL listed control panels only. The capability of plug-
ging  this  detector  into  a  variety  of  special  bases  makes  it
more versatile than equivalent direct-wired models.
Two  LEDs  on  each  detector  provide  local  360°  visible
alarm indication. They flash every ten seconds indicating
that power is applied and the detector is working properly.
The  LEDs  latch  on  in  alarm.  Remote  LED  annunciator
capability  is  standard  and  may  be  implemented  through
an  optional  accessory  RA400Z.  The  alarm  can  be  reset
only  by  a  momentary  power  interruption.  This  detector
may be tested by activating the internal reed switch with
a magnet.
Base Selection And Wiring Guide
Refer  to  the  installation  instructions  for  the  Plug-in
Detector Bases for base selection and wiring instructions.
System Sensor has a variety of detector bases available for
Specifications
Size
Height:
1.7 inches (43 mm)
Diameter:
4.0 inches (101 mm)
Weight:
3.6 oz. (102 g)
Operating Temperature Range:
0°C to 49°C (32°F to 120°F)
Operating Humidity Range:
10% to 93% Relative Humidity noncondensing
Latching Alarm:
Reset by momentary power interruption.
this smoke detector, including 2-wire applications with and
without relays and/or current limiting resistors, 4-wire and
120VAC applications.
All  bases  are  provided  with  screw  terminals  for  power,
ground, remote annunciator connections and relay contact
connections,  if  applicable.  The  electrical  ratings  for  each
detector-base  combination  are  also  included  in  the  base
installation instructions.
Installation
NOTE:
 All wiring must conform to applicable local codes,
ordinances, and regulations.
NOTE:  Verify  that  all  detector  bases  are  installed,  that
the initiating-device circuits have been tested, and
that  the  wiring  is  correct.  (Refer  to  detector  base
manual for testing procedure.)
WARNING
Remove power from initiating-device circuits before install-
ing detectors.
1. Install detectors:
 a.  Place the detector into the detector base.
 b. Turn  the  detector  clockwise  until  the  detector  drops
into place.
 c.  Continue  turning  detector  clockwise  to  lock  it  in
place.
2. Tamper Resistance: The detector bases can be made tam-
per resistant. When capability is enabled, detectors can-
not be removed from the base without the use of a tool.
See the detector base installation manual of the detector
base for details in using this capability.
3. After  all  detectors  have  been  installed,  apply  power  to
the control unit.