System Sensor 2151 Manuel D’Utilisation

Page de 4
D100-04-00
2
I56-581-07R
4. Test  the  detector  using  the  magnet  as  described  under
TESTING.
5. Reset the detector at the system control panel.
6. Notify the proper authorities that the system is back on
line.
CAUTION
Dust covers are an effective way to limit the entry of dust
into smoke detector sensing chambers. However, they may
not completely prevent airborne dust particles from enter-
ing the detector. Therefore, System Sensor recommends the
removal of detectors before beginning construction or other
dust producing activity.
Be  sure  to  remove  the  dust  covers  from  any  sensors  that
were left in place during construction as part of returning
the system to service.
CAUTION
Smoke  detectors  are  not  to  be  used  with  detector  guards
unless  the  combination  has  been  evaluated  and  found
suitable for that purpose.
Testing
Before testing, notify the proper authorities that the smoke
detector system is undergoing maintenance and will tem-
porarily  be  out  of  service.  Disable  the  zone  or  system
undergoing  maintenance  to  prevent  unwanted  alarms.
Detectors  must  be  tested  after  installation  and  as  part  of
periodic maintenance. Test the 2151 as follows:
NOTE:  Before  testing  the  detector,  check  to  ensure  the
LEDs blink. If they do not, the detector has lost
power (check the wiring) or it is defective (return
it for repair).
LED
LED
TEST MODULE
SOCKET
TES
T
MA
G
NE
T
PAINTED
SURFACE
Figure 1. Bottom and side views showing position of test magnet:
A. Test Magnet (p/n M02-04-01 or M02-09-00)
 1. Place  the  magnet  against  the  cover  in  the  location
designated by the raised mark to activate the test fea-
ture (see Figure 1).
 2. The LEDs should latch ON within 5 seconds indicat-
ing alarm and annunciating the panel.
B. Test Module ( MOD400R)
 Use  the  MOD400R  with  a  DMM  or  voltmeter  to  check
the  detector  sensitivity  as  described  in  the  MOD400R
manual.
C. Aerosol Generator (Gemini 501)
 Set the generator to represent 4% to 5%/ft. obscuration
as described in the Gemini 501 Manual. Using the bowl-
shaped applicator, apply aerosol until unit alarms.
Notify  the  proper  authorities  that  the  system  is  back  on
line.
Detectors that fail these tests should be cleaned as described
under  MAINTENANCE  and  retested.  If  the  detectors  still
fail these tests, they should be returned for repair.
Maintenance
It  is  recommended  that  the  detector  be  removed  from
its  mounting  base  to  facilitate  cleaning.  The  detector  is
cleaned as follows:
NOTE:  Before  removing  the  detector,  notify  the  proper
authorities  that  the  smoke  detector  system  is
undergoing  maintenance  and  will  be  temporarily
out of service. Disable the zone or system undergo-
ing maintenance to prevent unwanted alarms.
C0627-00