System Sensor Intelligent Air Duct Smoke Detector Housing Manuel D’Utilisation

Page de 12
D500-08-00 
I56-512-07R
DH500 Intelligent Air Duct Smoke 
Detector Housing
INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS
 3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Before Installing 
Please  thoroughly  read  System  Sensor’s  Guide  for  Proper 
Use of Smoke Detectors in Duct Applications 
(I56-473-XX), 
which  provides  detailed  information  on  detector  spac-
ing,  placement,  zoning,  wiring,  and  special  applications. 
Copies  of  this  manual  are  available  from  System  Sensor. 
NFPA Standards 72 and 90A should also be referenced for 
detailed information. 
NOTICE: This manual should be left with the owner/user 
of this equipment.
IMPORTANT: This detector must be tested and maintained 
regularly  following  NFPA  72  requirements.  The  detector 
should be cleaned at least once a year.
General Description
An HVAC system supplies conditioned air to virtually every 
area of a building. Smoke introduced into this air duct sys-
tem will be distributed to the entire building. Smoke detec-
tors designed for use in air duct systems are used to sense 
the presence of smoke in the duct.
The  DH500  Air  Duct  Detector  Housings  are  used  with 
System Sensor’s intelligent model 1551 ionization detector 
head and model 2551 photoelectronic detector head. These 
two principal smoke detection methods are combined with 
an efficient housing design that samples air passing through 
a duct and allows early detection of a developing hazardous 
condition. When sufficient smoke is sensed, an alarm signal 
is initiated at the fire control panel monitoring the detector, 
and  appropriate  action  can  be  taken  to  shut  off  fans  and 
Specifications
Length: 
14.5 inches  (36.7 cm)
Width: 
5 inches 
(12.7 cm)
Depth: 
3.5 inches 
(8.9 cm)
Weight: 
2.8 lbs. 
(1.1 kg)
Operating Temperature Range: 
32° to 120°F (0° to 49°C)
Operating Humidity Range: 
10% to 93% Relative Humidity
Duct Air Velocity: 
500 – 4000 ft./min. (91.4 – 1219.2 m/min.)
Electrical Ratings for DH500
Voltage Range: 
14.5 – 32 VDC Peak
Standby Current (nominal): 
150uA at 24 VDC
Power-Up Surge at Max.
    Rated Voltage: 
1.5mA-sec.
LED current (nominal): 
6mA at 24 VDC
blowers,  change  over  air  handling  systems,  etc.  This  can 
prevent the distribution or isolation of toxic smoke and fire 
gases throughout the areas served by the duct system.
Two  LEDs  on  each  detector  latch  ON  to  provide  a  local 
alarm  indication.  There  is  also  a  remote  alarm  output 
for  use  with  auxiliary  devices.  The  DH500  has  remote 
test  capability  with  the  RTS451/RTS451KEY  Remote  Test 
Station.
Contents of the Duct Detector Housing Kit
The DH500 consists of the following items: (See Figure 1.)
See Note 1 on Page 2 for inlet sampling tube and detector
supply information.
1.  Complete housing base and cover assembly.
2.  Two #10 sheet metal mounting screws.
3.  Two sampling tube filters.
4.  One test magnet.
5.  Drilling template.
6.  Two 5/16-inch O-rings.
7.  Two rubber tube bushings seals.
8.  Four #6 self-tapping mounting screws for the sampling 
tube.
9.  One filter adapter.
10.  One inlet tube end plug.
11.  Four #6x7/10 cover mounting screws.
12.  Two #10 speed nuts.
13.  One test coil and parts bag.