System Sensor Intelligent Air Duct Smoke Detector Housing Manuel D’Utilisation

Page de 12
D500-08-00 
I56-512-07R
NOTE:  The  inlet  sampling  tube  must  be  ordered  sepa-
rately. It must be the correct length for the width 
of the duct where it will be installed. See Table 1 to 
determine the inlet tube required for different duct 
widths.  Smoke  detector  heads  (1551,  ionization; 
2551, photoelectronic) must be ordered separately.
Installation Sequence 
Page
Step 1.  Verify duct air flow direction and velocity 
2
Step 2.  Drill the mounting holes 
3
Step 3.  Secure the housing base to the duct 
3
Step 4.  Install the inlet sampling tube 
3
Step 5.  Field wiring 
5
Step 6.  Install the filters and check pressure differential  5
Step 7.  Perform detector check 
7
Step 8.  Install the cover 
8
Step 9.  Perform the final system check (Testing) 
8
Step 1. Verify Duct Air Flow Direction and Velocity
The DH500 is designed to be used in air handling systems 
having air velocities of 500 to 4000 feet per minute. Be sure 
to  check  engineering  specifications  to  ensure  that  the  air 
velocity in the duct falls within these parameters. If neces-
sary, an Alnor Model 6000-P velocity meter, Dwyer 460 dif-
ferential pressure gauge, or their equivalent, may be used 
to check the air velocity in the duct.
H0297-00
SAMPLING TUBE
FILTERS
CONDUIT HOLES
DUCT DETECTOR 
HOUSING
TERMINAL STRIP
DUCT DETECTOR
COVER
SAMPLING TUBE
MOUNTING
SCREWS
DETECTOR HEAD
(SUPPLIED SEPARATELY)
EXHAUST 
FILTER ADAPTER
DETECTOR BASE
INLET SAMPLING TUBE
(SUPPLIED SEPARATELY)
O-RINGS
FOAM
GASKETS
HOUSING
MOUNTING SCREWS
TEST MAGNET
TUBE
END
PLUG
Figure 1:
Step 2. Drill the Mounting Holes
Remove the paper backing from the top and bottom of the  
template. Affix the template to the air duct at the desired 
mounting  location.  Make  sure  the  template  lies  flat  and 
smooth  on  the  air  duct.  Center  punch  hole  targets  and 
remove  the  template.  Drill  the  holes  as  indicated  on  the 
template. Slide the two speed nuts over the two small holes 
(Hole A) next to the sampling tube bushing holes (Hole B) 
previously drilled in the duct. (See Figure 2.)
Step 3. Mount Duct Housing
Remove the duct housing cover. Slide the foam gaskets over 
the  tube  bushings  as  shown  in  Figure  2B.  Make  sure  the 
two small holes in the gaskets line up with the two base 
mounting holes. Put one 5/16-inch O-ring over each of the 
two #10 sheet metal screws. Use the two sheet metal screws 
to secure the duct housing to the duct.
CAUTION
 
Do not overtighten the screws.