A
Building Safety. Building Security.
IS Thermal Detector AWEX-55000-440
The  addressable  Intrinsically  Safe  Thermal  Detector 
AWEX-55000-440  (fi g. B)  uses  the  heat  principle  and 
was  developed  for  the  fi re  detection  in  hazardous 
areas.  The  heat  detector  must  always  be  connected 
via a safety barrier, which has been approved for this 
detector, and a protocol interface. Furthermore, the re-
levant  country  specifi c  regulations  always  have  to  be 
observed.
The detector is assigned to Class A2S and can be used 
up to a room height of 6m. Depending on the parameter 
setup in the fi re detection control panel, the detector 
can operate either as maximum heat detector with an 
alarm temperature of 55°C, or as rate-of-rise heat de-
tector with a maximum temperature of 55°C.
The proven ADM loop technology with Apollo/Discovery 
protocol establishes a permanent communication bet-
ween the fi re detection control panel and the detector. 
That ensures a periodical function testing of the detec-
tor.  Fires  are  safely  detected  in  the  control  panel  by 
continuously analysing the measured values.
The two LEDs with 360° visibility indicate the activated 
condition of the detector. The detector address is se-
lected by means of a code card in the detector base. 
Therefore the detector can be changed without additi-
onal tools.
The detector is inserted into the IS Detector Base ASEX-
45681-215  (not  illustrated)  and  it  can  be  protected 
against theft.
Specifi cations
Ignition protection 
intrinsically safe
Ex classifi cation 
EEx ia IIC T5
Operating voltage 
Supply through loop voltage
Current consumption 
typ. 300µA (quiescent)
Ambient temperature 
 -20°C to +40°C (Class T5, no condensation or icing)
-20°C to +60°C (Class T4, no condensation or icing)
Relative humidity 
0 – 95% (no condensation)
Dimensions ø × H 
100 × 42 (mm)
Colour 
white
Weight 
100g
Approval 
EECS ATEX 0073
 
LPCB 010p
Order number 
242036
Order name 
IS Thermal Detector/Anal./XP95/Apo AWEX-55000-440
IS Detector Base ASEX-45681-215
The IS Detector Base ASEX-45681-215 is designed to 
accommodate intrinsically safe intelligent fi re detectors 
Series XP95 for use in ADM loops with Apollo/Discovery 
protocol.
Due to its robust multi-wire screw terminals, the detec-
tors can be wired with ease, thus achieving a secure 
and durable connection.
The detector address is selected by means of a code
card in the detector base. Therefore the detector can
be changed without additional tools.
The base is designed for surface mounting in hazardous 
areas. A mechanical theft protection of the detector can 
optionally be activated at the detector base.
Approval 
EECS ATEX 0073
 
LPCB 010q
Order number 
241024
Order name 
IS Optical Smoke Detector/Anal./XP95/Apo AOEX-55000-640