LST AOEX-55000-640 Manuel D’Utilisation

Page de 3
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
Ex-ApoDisc_DBL_LST_EN_0804.PDF • PAGE 3
A
Building Safety. Building Security.
The Protocol Interface API-55000-855 (fi g. D) serves for 
the design of an intrinsically safe electric circuit in ADM 
loop technology. It allows the bidirectional data traffi c 
between fi re detection control panel and detectors in 
hazardous areas, via an ADM loop with Apollo/Discove-
ry protocol. The interface is always used together with 
the Safety Barrier AES-29600-098.
Protocol Interface API-55000-855
Ignition protection 
intrinsically safe
Ex classifi cation 
EEx ia IIC T5
Operating voltage 
Supply through loop voltage
Current consumption at 24V 
1mA
Ambient temperature 
-10°C to +60°C
Relative humidity 
10 – 95% (no condensation)
Dimensions W × H × D 
93 × 110 × 20 (mm)
Weight 
100g
Order number 
228005
Order name 
Protocol Interface/Anal./XP95/Apo API-55000-855
Specifi cations
Safety Barrier AES-29600-098
The Safety Barrier AES-29600-098 (fi g. C) is used for 
intrinsically safe electric circuits. The  built-in zener bar-
rier and the safe galvanic isolation allow the connection 
of fi re detectors in hazardous areas. Due to the galvanic 
isolation, the earth leakage monitoring can remain acti-
vated in the fi re detection control panel.
Ignition protection 
intrinsically safe
Ex classifi cation 
EEx ia IIC T5
Operating voltage 
Supply through loop voltage
Ambient temperature 
-10°C to +60°C
Colour 
green
Approval 
EECS ATEX 0073
Order number 
228004
Order name 
Safety Barrier/Anal./XP95/Apo AES-29600-098
Specifi cations
Ambient temperature 
-20°C to +60°C (no condensation or icing)
Relative humidity 
10 – 95% (no condensation)
Dimensions ø × H 
100 × 15 (mm)
Colour 
white
Weight 
50g
Order number 
246027
Order name 
IS Detector Base/Anal./Apo ASEX-45681-215
Specifi cations