Honeywell 25/50ZS Manuel D’Utilisation

Page de 144
112
Audio Command Center Series Manual — P/N 51889:E1  6/8/2010
Programmed Activation by FACP
MS-9600, MS-9200UDLS and MS-9200UD
Message Assignment - Zone Specific
The FACP can be programmed to allow a specific addressable input device to generate one of five 
messages over any speaker circuit.  Any one of the five messages can be programmed to each of the 
available zones (Zone 1 through Zone 99).  In the following examples, assume that Zone 5 is pro-
grammed to Message 1, Zone 7 is programmed to Message 2, Zone 8 is programmed to Message 3, 
and Zone 35 is not programmed to a message.
if two devices are being programmed and the first addressable input device is programmed to 
Zone 7 and Zone 35, and a second addressable input device is programmed to Zone 5 and Zone 
35, activation of the first addressable input device (address 12 in the example below) will 
cause Message 2 to be generated over speaker circuit 3.  (Table D.5 on page 109).  If the sec-
ond addressable device (address 20 in the example below) is also activated, Message 1 will 
now be transmitted over speaker circuit 3 since Message 1 has a higher priority then Message 
2.
Programming is accomplished in the same manner as previously described.
To Program one of five messages to a speaker zone, press the ENTER key at the FACP.  The 
following screen will be displayed: 
Zone 5    and    Zone 35
Zone 7    and    Zone 35
Addressable Pull Station
(address 12)
Message 1
(highest priority of the three )
programmed to
activate
Speaker Circuit 3
Addressable Pull Station
(address 20)
programmed to
Message 2
(2nd highest priority of the three)
activate
1=READ STATUS MODE
2=PROGRAMMING MODE
3=MANUAL DIAL MODE