Audio Command Center Series Manual — P/N 51889:E1  6/8/2010
115
MS-9600, MS-9200UDLS and MS-9200UD
Programmed Activation by FACP
Fire Fighter Telephone SLC Point Assignment
If annunciation of remote FFT locations is desired on the ACC-FFT keypad, an addressable input 
device must be programmed as a PHONE type on the MS-9200UDLS or MS-9600.
Program each addressable input device as a PHONE type as described in the appropriate FACP 
manual.  SLC point programming can be accessed by entering Programming Mode and selecting 
Point Program from the list of programming options.
The following table lists the SLC points dedicated for FFT annunciation:   
FFT Number on ACC-FFT Keypad
MS-9200UDLS SLC Point Number
(ACS Address 05)
MS-9600 SLC Point Number
(ACS Address 07)
FFT Inputs can be installed only 
on SLC Loop #1
1
75
135
2
76
136
3
77
137
4
78
138
5
79
139
6
80
140
7
81
141
8
82
142
9
83
143
10
84
144
11
85
145
12
86
146
13
87
147
14
88
148
15
89
149
16
90
150
17
91
151
18
92
152
19
93
153
20
94
154
21
95
155
22
96
156
23
97
157
24
98
158