Honeywell 25/50ZS Manuel D’Utilisation

Page de 144
30
Audio Command Center Series Manual — P/N 51889:E1  6/8/2010
Product Description
Getting Started
An ACC-25/50ZST does not require an FC-MIM since the function of this module is incorporated 
in the ACC-FFT Fire Fighter Telephone module which is included with the ACC-25/50ZST.  The 
Remote Microphone Module is connected directly to the ACC-FFT Fire Fighter Telephone module 
(refer to Section “ACC-FFT Fire Fighter Telephone Module (ACC-25/50ZST Only)” on page 55.
ACC-EPM External Page Module
This optional module provides an interface to external non-emergency paging equipment.  When 
activated, a contact closure will switch the external paging equipment into the ACC-25/50 Series 
speaker circuits if the circuits have not been activated by the ACC-25/50 Series panels for emer-
gency use.  Any emergency/fire activation or local paging will override the ACC-EPM input.  Pag-
ing from non-emergency equipment is prohibited during AC loss condition to preserve battery 
power.
1.7  Getting Started
This section describes the basic guidelines for setting up the various ACC-25/50 Series systems, 
assuming that the speaker and FACP cabling has been installed.
1.7.1  ACC-25/50, Requiring up to 50 Watts of Audio Power
Install backboxes and circuit boards as described in Section 3,  ”Installation” on page 42.  
Configure the ACC-25/50 for Single Zone operation, if individual speaker circuit control is not 
required, by setting DIP switch S3 switches 1, 2 and 3 on the ACC-MCB mother board.  The 
factory default setting is Dual Zone output control.  Refer to Section 2,  ”Field Programming” 
on page 32
.
Record any new voice messages as described in Section 4,  ”Operating Instructions” on page 
63.
1.7.2  ACC-25/50 With ACC-25/50DA(s), Requiring Greater Than 50 
Watts of Audio Power
Connect the Audio Riser and Master Command Bus (for All-Call) cabling between the ACC-
25/50 and ACC-25/50DA panels.  Refer to Section 5,  ”Application Examples” on page 80.
Install backboxes and circuit boards as described in Section 3,  ”Installation” on page 42.
Configure the ACC-25/50 for Single Zone operation using DIP switch S3 switches 1, 2 and 3 
on the ACC-MCB motherboard.  Refer to Section 2,  ”Field Programming” on page 32.  The 
ACC-25/50DA DIP switches can be left at the default settings.
Record any new voice messages as described in Section 4,  ”Operating Instructions” on page 
63.
1.7.3  ACC-25/50ZS & ACC-25/50ZST, Requiring up to 50 Watts of 
Audio Power
Install backboxes and circuit boards as described in Section 3,  ”Installation” on page 42.
Configure the ACC-25/50ZS/T for Single Zone operation using DIP switch S3 switches 1, 2 
and 3 on the ACC-MCB motherboard.  Refer to Section 2,  ”Field Programming” on page 32.
Configure the ACC-ZPM Zone Page Module DIP switch S1 switches 1, 2 and 3 for operation 
with the FACP.  Refer to Section 2,  ”Field Programming” on page 32 and Section 5,  
”Application Examples” on page 80
.
NOTE: Paging operations initiated from within the ACC-25/50 Series main panel will override the 
remote microphone.