Honeywell 25/50ZS Manuel D’Utilisation

Page de 144
64
Audio Command Center Series Manual — P/N 51889:E1  6/8/2010
Operating Instructions
Switch Functions
4.1.3  RECORD/PLAYBACK
– for recording messages when Record/Bypass switch is in the up Record position (refer to 
– for reviewing recorded message when Record Bypass Switch is in the down Bypass position 
(requires optional FC-LPS module).
4.1.4  TROUBLE SILENCE
– momentary depression silences the local piezo when system is in trouble condition.  
4.1.5  Record/Playback Button - Record Customized Messages
The key labeled Record/Playback is used for recording customized messages.  
Recording Instructions
Recording a custom message or messages into the ACC-25/50 Series requires that the voice mes-
sage(s) be input via the internal microphone or via the RCA or mini PC Jack.  After recording a 
new voice message, wait approximately one minute for internal supervision to take place before 
broadcasting the new message over the building speakers. Refer to Figure 2.1 and Figure 2.2 on 
page 33
 for switch locations.
1. Confirm the Message Control settings on S3 DIP switches 1, 2, and 3.  These settings will 
determine the number of messages that can be recorded and duration of each (refer to Table 2.7 
on page 37
).
2. The background music feature, which is selected by S5 DIP switch 3, must be disabled in order 
to record a new voice message.
3. Enable recording by setting S5 DIP switch 8 to the ON position.  The Record/Playback push-
button is now ready to be used in record operation.
4. Select the record input source by setting S5 DIP switch 7 to the OFF position if recording via 
the microphone, or to the ON position if recording via one of the External Audio Input Jacks.  
page 19.
5. Slide the Record Bypass switch S2 to the UP position to enable the message storage device.
6. Note the following while recording:
To alert the user that there is only two seconds of record time remaining, the LED on the 
Record/Playback push-button will change from steady-on to flashing.
The system Trouble LED and Trouble Relay will be on while recording but the Trouble 
Sounder will remain off.  The system will not respond to the CMD inputs or Zone activation 
buttons while recording
It is not necessary to fill the entire record time.  The time limits represent the maximum time 
allotted.  
Factory default messages are replaced with the custom messages recorded from the External 
Audio Input jacks or internal microphone.
7. Press and release the Record/Playback push-button.  This will cause the Record/Playback LED 
and Message push-button LEDs, as configured by S3 DIP switches 1, 2, and 3 (see Table 2.7 
on page 37), to flash on and
 off.  In addition, the panel will indicate a trouble condition since it 
cannot be alarm activated.
NOTE: For proper system operation, the voice message length must be at least 8 seconds long.