Audio Command Center Series Manual — P/N 51889:E1  6/8/2010
Operating Instructions
Operation
Emergency Page Using Local/Integral Microphone
Pressing the local microphone push-to-talk switch will interrupt the tone/voice message and direct 
paging audio to the Audio Amplifier Module (ACC-AAM25) speaker circuit(s).  The system will 
revert back to the tone/voice message if the microphone key is held for more than 3 minutes.
Emergency Page Using Optional Remote Microphone
Pressing the remote microphone push-to-talk switch will interrupt the tone/voice message and 
direct paging audio to the Audio Amplifier Module (ACC-AAM25) speaker circuit(s).  The system 
will revert back to the tone/voice message if the remote microphone key is held for more than 3 
minutes.  Note that Remote Microphone All-Call functionality is DIP switch programmable for the 
ACC-25/50.  Set the DIP switch to OFF if only activating ACC-25/50 speaker circuits is desired.  
Refer to Section “S3 DIP Switch Settings on ACC-25/50 Motherboard (ACC-MCB)” on page 37.
4.5.9  Paging: ACC-25/50 Dual Zone
When the ACC-25/50 is configured for Dual Zone operation, the speaker circuits connected to each 
Audio Amplifier Module (ACC-AAM25) are controlled individually by the Zone 1 and Zone 2 
push-buttons.  Paging is performed on a select by zone basis.  Note that paging from the local/inte-
gral microphone will override paging operations from the optional Remote Microphone.
General Page Using Local/Integral Microphone
Selecting the Zone 1 and/or Zone 2 push-buttons(s) and pressing the local microphone push-to-talk 
switch will direct paging audio to the speaker zone(s).
General Page Using Optional Remote Microphone
Pressing the remote microphone push-to-talk switch will direct paging audio to the Audio Ampli-
fier Module (ACC-AAM25) speaker zone(s).  Note that Remote Microphone All-Call functionality 
is DIP switch programmable for the ACC-25/50.  Set the DIP switch to OFF for Dual Zone config-
uration.  Refer to Section “S3 DIP Switch Settings on ACC-25/50 Motherboard (ACC-MCB)” on 
page 37.
Emergency Page Using Local/Integral Microphone
Pressing the local microphone push-to-talk switch during an FACP activated alarm will interrupt 
the tone/voice message and direct paging audio to non manually deactivated speaker zones.  Emer-
gency paging to non-FACP activated speaker zones may be performed by selecting the speaker 
zones (Zone 1 and/or Zone2) and pressing the microphone push-to-talk switch.  The system will 
revert back to the tone/voice message if the microphone key is held for more than 3 minutes.
Emergency Page Using Optional Remote Microphone
Pressing the remote microphone push-to-talk switch during an FACP activated alarm will interrupt 
the tone/voice message and direct paging audio to non manually deactivated speaker zones.  The 
system will revert back to the tone/voice message if the remote microphone key is held for more 
than 3 minutes.  Note that Remote Microphone All-Call functionality is DIP switch programmable 
for the ACC-25/50.  Set the DIP switch to OFF for Dual Zone configuration.  Refer to Section “S3 
DIP Switch Settings on ACC-25/50 Motherboard (ACC-MCB)” on page 37.
4.5.10  Paging: ACC-25/50ZS & ACC-25/50ZST
Refer also to Section “All-Call: ACC-25/50ZS & ACC-25/50ZST” on page 72 for All-Call type 
paging operation.  In this system configuration, the Zone Page Module (ACC-ZPM) permits paging 
by zone.
General Page Using Local/Integral Microphone
Selecting any of the Zone push-buttons(s) on the Zone Page Module (ACC-ZPM) and pressing the 
local microphone push-to-talk switch will direct paging audio to the speaker circuit(s).