Status alarms and Status Alarm Severity
 (continued)
Table 5-2:   
Alarm code
Status message
Default severity Notes
Configurable?
A103
Data Loss Possible (Totals
and Inventories)
Informational
Applies only to flowmeters with the
standard core processor.
Can be set to either Informational or
Ignore
, but cannot be set to Fault.
Yes
A104
Calibration in Progress
Informational
Can be set to either Informational or
Ignore
, but cannot be set to Fault.
Yes
A105
Slug Flow
Informational
Yes
A106
Burst Mode Enabled
Informational
Can be set to either Informational or
Ignore
, but cannot be set to Fault.
Yes
A107
Power Reset Occurred
Informational
Normal transmitter behavior; oc-
curs after every power cycle.
Yes
A108
Basic Event 1 On
Informational
Applies only to basic events.
Yes
A109
Basic Event 2 On
Informational
Applies only to basic events.
Yes
A110
Frequency Output Satura-
ted
Informational
Can be set to either Informational or
Ignore
, but cannot be set to Fault.
Yes
A111
Frequency Output Fixed
Informational
Can be set to either Informational or
Ignore
, but cannot be set to Fault.
Yes
A112
Upgrade Transmitter Soft-
ware
Informational
Applies only to systems with trans-
mitter software earlier than v5.0.
Yes
A113
mA Output 2 Saturated
Informational
Can be set to either Informational or
Ignore
, but cannot be set to Fault.
Yes
A114
mA Output 2 Fixed
Informational
Can be set to either Informational or
Ignore
, but cannot be set to Fault.
Yes
A115
No External Input or Polled
Data
Informational
Yes
A118
Discrete Output 1 Fixed
Informational
Can be set to either Informational or
Ignore
, but cannot be set to Fault.
Yes
A119
Discrete Output 2 Fixed
Informational
Can be set to either Informational or
Ignore
, but cannot be set to Fault.
Yes
A131
Meter Verification in Pro-
gress: Outputs to Last
Measured Value
Informational
Applies only to transmitters with
Smart Meter Verification.
Yes
A132
Sensor Simulation Active
Informational
Applies only to flowmeters with the
enhanced core processor.
Can be set to either Informational or
Ignore
, but cannot be set to Fault.
Yes
A141
DDC trigger(s) have com-
pleted
Informational
Applies only to flowmeters with the
enhanced core processor.
Can be set to either Informational or
Ignore
, but cannot be set to Fault.
Yes
Configure device options and preferences