Emerson 9739 Manuel D’Utilisation

Page de 256
Procedure
Set Discrete Output Fault Action as desired.
The default setting is None.
Options for Discrete Output Fault Action
Options for Discrete Output Fault Action
Table 6-10:   
Label
Discrete output behavior
Polarity=Active High
Polarity=Active Low
Upscale
Fault: discrete output is ON
(site-specific voltage)
No fault: discrete output is con-
trolled by its assignment
Fault: discrete output is OFF
(0 V)
No fault: discrete output is con-
trolled by its assignment
Downscale
Fault: discrete output is OFF
(0 V)
No fault: discrete output is con-
trolled by its assignment
Fault: discrete output is ON
(site-specific voltage)
No fault: discrete output is con-
trolled by its assignment
None
 (default)
Discrete output is controlled by its assignment
Fault indication with the discrete output
To indicate faults via the discrete output, set parameters as follows:
Discrete Output Source
 = Fault
Discrete Output Fault Action
 = None
Note
If Discrete Output Source is set to Fault and a fault occurs, the discrete output is always ON. The setting
of Discrete Output Fault Action is ignored.
6.4
Configure the discrete input
The discrete input is used to initiate one or more transmitter actions from a remote input
device. Your transmitter has one discrete input.
The discrete input parameters include:
Discrete Input Action
Discrete Input Polarity
Integrate the meter with the control system
Configuration and Use Manual 
103