Table 6-11:   
Action
Label
Display
ProLink II
ProLink III
Field Communicator
Reset gas standard
volume total
RESET GSVT
Reset Gas Std Volume
Total
Reset Gas Std Volume
Total
Reset gas standard vol-
ume total
Reset all totals
RESET ALL
Reset All Totals
Reset All Totals
Reset totals
Petroleum measurement
Reset temperature-
corrected volume to-
tal
TCVOL
Reset API Ref Vol Total
Reset Volume Total at
Reference Temperature
Reset corrected volume
total
Concentration measurement
Reset CM reference
volume total
RESET STD V
Reset CM Ref Vol Total
Reset Volume Total at
Reference Temperature
Not available
Reset CM net mass to-
tal
RESET NET M
Reset CM Net Mass Total Reset Net Mass Total
Not available
Reset CM net volume
total
RESET NET V
Reset CM Net Vol Total
Reset Net Volume Total
Not available
Increment CM matrix
INCr CURVE
Increment Current CM
Curve
Increment Concentration
Matrix
Not available
CAUTION!
Before assigning actions to an enhanced event or discrete input, check the status of the event
or the remote input device. If it is ON, all assigned actions will be performed when the new
configuration is implemented. If this is not acceptable, wait until an appropriate time to assign
actions to the event or discrete input.
6.4.2
Configure Discrete Input Polarity
Display
OFF-LINE MAINT
 > OFF-LINE CONFG > IO > DI > DI POLAR
ProLink II
ProLink
 > Configuration > Discrete Input > DI1 Polarity
Field Communicator Configure > Manual Setup > Inputs/Outputs > Discrete Input > Polarity
Overview
The discrete input has two states: ON and OFF. Discrete Input Polarity controls how the
transmitter maps the incoming voltage level to the ON and OFF states.
Procedure
Set Discrete Input Polarity as desired.
The default setting is Active Low.
Integrate the meter with the control system
Configuration and Use Manual 
105