Ratings
Notes:
1.  Shield water heaters require special gas venting. Use 
only the vent materials and methods specified in the  
Shield Installation and Service Manual.  
2.  Standard Shield water heaters are equipped to operate 
from sea level to 4,500 feet only with no adjustments.  
The water heater will de-rate by 4% for each 1,000 feet 
above sea level up to 4,500 feet.
3.  High altitude Shield water heaters are equipped to 
operate from 3,000 to 12,000 feet only with no field 
adjustments. The water heater will de-rate by 2% for 
each 1,000 feet above 3,000 feet. High altitude models 
are manufactured with a different control module 
for altitude operation, but the operation given in this 
manual remains the same as the standard models. A 
high altitude label (as shown in FIG. A) is also affixed 
to the unit.
7
Maximum allowed working pressure is located on the rating plate.
Model Number
Note: Change “N” 
to “L” for L.P. gas 
models.
CSA
Input Modulation Btu/hr
(Note 2)
Water Content 
Gallons
Water 
Connections
Gas 
Connections
Vent/Air Size
        
  
         
Min
 
                Max
(Note 1)
SNR150-100
30,000 - 150,000
92
1-1/2"
1/2"
3"
SNR200-100
40,000 - 199,999
93
1-1/2"
1/2"
3"
SNA285-125
57,000 - 285,000
124
2"
3/4"
4"
SNA400-125
80,000 - 399,999
125
2"
1"
4"
SNA500-125
100,000 - 500,000
126
2"
1"
4"
 NOTICE
Figure A High Altitude Label Location
UNIT EQUIPPED FOR
3,000 FT. TO 12,000 FT.
HIGH ALTITUDE
       
Installation & Service Manual