Lochinvar SNA285-125 Manuel D’Utilisation

Page de 76
1/4”  MIINIMUM CLEARANCE
AROUND HOT WATER PIPING
1” MINIMUM CLEARANCE
AROUND VENT PIPE
OPEN 
FRONT
Figure 1-2 Alcove Installation - Minimum Required Clearances
   6"
   6"
1/4” (6.35 MM)
MINIMUM CLEARANCE
AROUND HOT WATER PIPES
1” (25.4 MM) 
MINIMUM CLEARANCE
AROUND VENT PIPE
VENTILATING
AIR OPENING
CLOSED DOOR
VENTILATING 
AIR OPENING
AREA OF EACH OPENING: 
1 SQ. INCH PER 1000 BTU PER HOUR INPUT 
WITH ALUMINUM OF 100 SQ. INCHES
Figure 1-1 Closet Installation - Minimum Required Clearances
 WARNING
9
1  
Determine water heater location 
(continued)
RECOMMENDED SERVICE 
CLEARANCES:
Top 
-       
  18" (457 mm)
Left/Right Side -  24" (610 mm)
Front -           
  24" (610 mm)
RECOMMENDED SERVICE 
CLEARANCES:
Top 
-       
  18" (457 mm)
Left/Right Side -  24" (610 mm)
Front -           
  24" (610 mm)
       
Installation & Service Manual
TM
 WARNING
For closet installations, CPVC, 
polypropylene or stainless steel 
vent material MUST BE used in 
a closet structure due to elevated 
temperatures.  Failure to follow 
this warning could result in fire, 
personal injury, or death.
For alcove installations, CPVC, 
polypropylene or stainless steel 
vent material MUST BE used 
in an alcove structure due to 
elevated temperatures.  Failure to 
follow this warning could result 
in fire, personal injury, or death.