VENTING FIREPLACE - REAR
To Use the Vent Graph (Figure 29)
1.  Determine  the  height  of  the  center  of  the 
horizontal vent pipe. Using this dimension on 
the  Sidewall  Vent  Graph,  locate  the  point  it 
intersects with the slanted graph line.
2.  From the point of this intersection, draw a vertical 
line to the bottom of the graph.
3.  Select the indicated dimension, and position the 
unit in accordance with same.
EXAMPLE A:
If the vertical dimension from the floor of the unit 
is 12 feet, the horizontal run to the outer wall flange 
must not exceed 12.3 feet.
EXAMPLE B:
If the vertical dimension from the floor of the unit 
is 6 feet, the horizontal run to the outer wall flange 
must not exceed 6.5 feet.
SPECIAL  NOTE:  For  each  45  degree  elbow 
installed  in  the  horizontal  run,  the  length  of  the 
horizontal run MUST be reduced by 18" (45cm). 
This does not apply if the 45 degree elbows are 
installed on the vertical part of the vent system. 
Reduce 3' for every 90° elbow.
Example: According  to  the  chart  the  maximum 
horizontal vent length is 20' and if two 45 degree 
elbows are required in the horizontal vent it must 
be reduced to 17'.
The  maximum  number  of  45  degree  elbows 
permitted  per  side  wall  installation  is  two  (2). 
These elbows can be installed in either the vertical 
or horizontal run.
Figure 29
  Acceptable vertical and horizontal vent run.
  Unacceptable vertical and horizontal vent run.
Venting Graph (Dimensions in Feet)
VERTICAL
DIMENSION
FROM
THE
BO
TTOM
OF
THE
UNIT
TO
THE
CENTER
OF
THE
FL
UE
OUTLET
WITH
VERTICAL
OR
HORIZONT
AL
TERMINA
TION
CAPS
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
B
A