WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS
Water vapor is a by-product of gas combustion. An unvented room 
heater produces approximately one (1) ounce (30ml) of water for 
every 1,000 BTU's (.3KW's) of gas input per hour. 
Unvented  room  heaters  must  be  used  as  supplemental  heat  (a 
room) rather than a primary heat source (an entire house). In most 
supplemental heat applications, the water vapor does not create a 
problem. In most applications, the water vapor enhances the low 
humidity atmosphere experienced during cold weather. 
The  following  steps  will  help  insure  that  water  vapor  does  not 
become a problem.  
1.  Be sure the heater is sized properly for the application, including 
ample combustion air and circulation air.
2.  If high humidity is experienced, a dehumidifier may be used to 
help lower the water vapor content of the air.
3.  Do not use an unvented room heater as the primary heat source 
(an entire house).
PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR
Provisions for Adequate Combustion and Ventilation Air
This heater shall not be installed in a confined space or unusually 
tight  construction  unless  provisions  are  provided  for  adequate 
combustion and ventilation air.
The National Fuel Gas Code, ANSI Z223.1 defines a confined space 
as a space whose volume is less than 50 cubic feet per 1,000 Btu per 
hour (4.8m
3
 per kw) of the aggregate input rating of all appliances 
installed in that space and an unconfined space as a space whose 
volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8m
3
 
per kw) of the aggregate input rating of all appliances installed in 
that space. Rooms communicating directly with the space in which 
the appliances are installed, through openings not furnished with 
doors, are considered a part of the unconfined space.
The following example is for determining the volume of a typical 
area in which the  SR-18 may be located and for determining if 
this area fits the definition of an unconfined space.
The maximum input of the  SR-18 is 18,000 Btu per hour.  Based 
on the 50 cubic feet per 1,000 Btu per hour formula, the minimum 
area that is an unconfined space for installation of the  SR-18 is 
900 cubic feet, 50 cubic feet x 18 = 900 cubic feet. To determine 
the cubic feet of the area in which the  SR-18 is to be installed, 
measure the length, width and height of the area.  Example:  The 
area  measures  13  feet  in  length,  9  feet  in  width  and  8  feet  in 
height, the area is 936 cubic feet.  The  SR-18 can be installed in 
this unconfined space with no requirement to provide additional 
combustion and ventilation air.
Warning: If the area in which the heater may be operated is smaller 
than that defined as an unconfined space or if the building is of 
unusually  tight  construction,  provide  adequate  combustion  and 
ventilation air by one of the methods described in the National Fuel 
Gas Code, ANSI Z223.1, Section 5.3 or applicable local codes.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough 
fresh air for combustion and ventilation. However, in buildings of 
unusually  tight  construction,  you  must  provide  additional  fresh 
air.
  Unusually tight construction is defined as construction where:
a.  Walls and ceilings exposed to the outside atmosphere have 
a continuous water vapor retarder with a rating of one perm 
or less with openings gasketed or sealed, and
b.  Weatherstripping has been added on openable windows and 
doors, and
c.  Caulking  or  sealants  are  applied  to  areas  such  as  joints 
around window and door frames, between sole plates and 
floors, between wall-ceiling joints, between wall panels, at 
penetrations for plumbing, electrical, and gas lines, and at 
other openings. 
If the heater is installed in a building of unusually tight construction, 
adequate air for combustion, ventilation and dilution of flue gases 
shall be provided in accordance with ANSI Z223.1/NFPA54.