Figure 35
A =   *Clearance above grade, veranda, porch, deck or balcony 
[*12 inches (30cm) minimum]
B =  clearance to window or door that may be opened [*12 
inches (30cm) minimum for appliances < 100,000 Btuh 
(30kW)
C =  clearance to permanently closed window [minimum 12 
inches (30cm) recommended to prevent condensation on 
window]
D =  vertical clearance to ventilated soffit located above the 
terminal  within  a  horizontal  distance  of  24  inches  (60 
cm) from the center of the terminal [18 Inches (46 cm) 
minimum
E  =  clearance  to  unventilated  soffit  [12  inches  30cm) 
minimum]
F  =  clearance to outside corner [See Page 20]
G =  clearance to inside corner [See Page 20]
H =  *not  to  be  installed  above  a  meter/regulator  assembly 
within 3 feet (90cm) horizontally from the center-line of 
the regulator
I  =  clearance to service regulator vent outlet [*6 feet (1.8m) 
minimum]
J  =  clearance to non-mechanical air supply inlet to building 
or  the combustion air inlet to  any  other appliance [*12 
inches (30cm) minimum for appliances ≤ 100,000 Btuh 
(30 kW)
 
  36 inches (90cm) minimum for appliances > 100,000 Btuh 
(30kW)]
K =  clearance to a mechanical air supply inlet [* 6 feet (1.8m) 
minimum]
L  =  †clearance  above  paved  sidewalk  or  a  paved  driveway 
located on public property [*7 feet (2.1m) minimum]
M =  clearance  under  veranda,  porch,  deck,  or  balcony  [*12 
inches (30cm) minimum ¥]
†    a  vent  shall  not  terminate  directly  above  a  sidewalk  or 
paved driveway which is located between two single family 
dwellings and serves both dwellings*
¥    only permitted if veranda, porch, deck, or balcony, is fully 
open on a minimum of 2 sides beneath the floor*
*    as specified in CGA B149 Installations Codes or ANSI 
Z223.1. Note: Local Codes or Regulations may require 
different clearances.
VENT CLEARANCES