Section 3. Installation
3.3.7
Typical 
installations
The example below in Figure 3-4 illustrates a Raptor system with terminators 
at both ends of the fieldbus segment as required in a F
OUNDATION
 fieldbus 
system. In this case terminators are enabled in the Rosemount 2410 Tank 
Hub and a Raptor field device at the end of the network segment. 
Figure 3-4. Example of Tankbus 
connection for a single tank
The maximum distance between the 2410 Tank Hub and the field devices on 
the tank depends on the number of devices connected to the Tankbus and the 
quality of cables. 
See chapter “Electrical Installation” in the Rosemount 2410 Reference 
Manual
 (Document no. 305030EN) for more information about cable 
selection, power budget, and the Raptor Tankbus.
See also “Typical Installations” in the Rosemount 2410 Reference Manual 
(Document no. 305030EN) for more examples of Raptor system installations.
Built-in terminator
 Tankbus
Built-in 
terminator 
enabled on the 
last device
2410 Tank Hub with 
intrinsically safe power 
supply, integrated power 
conditioner, and built-in 
terminator
Tankbus length up to 1000 meter depending 
on number of devices and cable quality
2240S Temperature 
Transmitter
5900S Radar 
Level Gauge
2230 Display