Section 3. Installation
3.3.6
The Tankbus
The Raptor system is easy to install and wire. Devices can be “daisy-chained” 
thus reducing the number of segment couplers.
In a Raptor system devices communicate with a Rosemount 2410 Tank Hub 
via the intrinsically safe Tankbus. The Tankbus complies with the FISCO
(1)
 
F
OUNDATION
 fieldbus standard. The Rosemount 2410 acts as power supply to 
the field devices on the Tankbus. 
Termination
A terminator is needed at each end of a F
OUNDATION
 Fieldbus network. 
Generally, one terminator is placed in the fieldbus power supply, and the other 
one in the last device in the fieldbus network. 
NOTE!
Ensure that there are two terminators on the fieldbus.
In a Raptor system the Rosemount 2410 Tank Hub acts as power supply. 
Since the 2410 normally is the first device in the fieldbus segment, the built-in 
termination is enabled at factory.
Other Raptor devices such as the Rosemount 5900S Radar Level Gauge, the 
Rosemount 2230 Graphical Field Display, and the Rosemount 2240S 
Multi-input Temperature Transmitter also have built-in terminators which can 
easily be enabled by inserting a jumper in the terminal block when necessary. 
Segment design
When designing a FISCO fieldbus segment a few requirements need to be 
considered. Cabling has to comply with FISCO requirements as described in 
“Cable Selection for the Tankbus” on page 3-7. 
You will also have to ensure that the total operating current of the connected 
field devices is within the output capability of the Rosemount 2410 Tank Hub. 
The 2410 is able to deliver 250 mA. Consequently, the number of field devices 
has to be considered so that the total current consumption is less than 
250 mA.
Another requirement is to ensure that all field devices have at least 9 V input 
voltage at their terminals. Therefore you will have to take into account the 
voltage drop in the fieldbus cables. 
Distances are normally quite short between the Rosemount 2410 Tank Hub 
and field devices on the tank. In many cases you can use existing cables as 
long as the FISCO requirements are fulfilled (see “Cable Selection for the 
Tankbus” on page 3-7)
.
See ”The Tankbus” in the Rosemount 2410 Reference Manual (Document no. 
305030EN) for more information on segment design of a Raptor system.
(1) FISCO=Fieldbus Intrinsically Safe Concept