DEFINITY Enterprise Communications Server Release 7 
Maintenance for R7r  
555-230-126  
Issue 4
June 1999
Maintenance Object Repair Procedures 
9-644
DS1-FAC (DS1 Facility) 
9
DS1 Converter Performance Measurements 
Report
The DS1 Converter Performance Measurements provide link performance 
measurements for the DS1 facilities.
When no facility alarms exist on the DS1 facility, events that indicate a 
degradation in the performance of the DS1 facility are monitored and recorded. 
These events will generate appropriate alarms when performance of the DS1 
facility has degraded below acceptable levels. These measurements include 
errored seconds, bursty seconds, severely errored seconds, and failed seconds.
There are two DS1 Converter Performance Measurements Sub-reports. The first 
sub-report, DS1 Converter Performance Measurements Summary Report, 
provides information on the worst 15 minute interval of data, the total for 24 hours 
of data and the current 15 minute counter for each of the above mentioned 
counters.
The second sub-report, DS1 Converter Performance Measurements Detailed 
Report displays a detailed log for the last 96 15-minute intervals for each of the 
above mentioned counters.
The DS1 Converter Performance Measurements Summary Report can be 
accessed with list measurements ds1-facility summary UUCSSf 
[print/schedule]
. A more detailed version of the report is accessed with list 
measurements ds1-facility log UUCSSf [print/schedule]
.
The user can reset all hardware and software measurement counters for a given 
facility with clear measurements ds1-facility UUCSSf. The 
Counted Since time 
is also reset and the 
Number of Valid Intervals count is set to zero.
The reports are printed on the screen or, by using the 
print option, on a printer 
attached to the terminal.
Clearing Firmware Errors
DS1 CONV error reports are generated by firmware autonomously, they are not 
associated with system technician demanded tests. Therefore, test board clear 
command does not affect the error status known by the DS1 CONV firmware. To 
clear all the on-board firmware-detected errors unconditionally, execute the clear 
firmware-counters
 command.