DEFINITY Enterprise Communications Server Release 7 
Maintenance for R7r  
555-230-126  
Issue 4
June 1999
Maintenance Object Repair Procedures 
9-1544
STRAT-3 (Stratum 3 Clock) 
9
Table 9-588.
TEST #161 Looparound Test 
Error 
Code
Test 
Result
Description/ Recommendation
1001
ABORT
The system could not allocate the necessary resources to run this test.
1. Retry the command at 1-minute intervals up to a maximum of 3 times.
1005
ABORT
This test aborts when it is run on a Stratum 4 system. Do not change 
synchronization to Stratum 3 without consulting the synchronization plan 
administrator for this switch.
2500
ABORT
Internal System Error 
1. Retry the command at 1-minute intervals a maximum of 3 times. 
1
FAIL
Either Reference A failed or CI card A failed. This condition usually indicates a 
failure of the DS1 reference; however, there may also be a failure of the CI card 
to which the reference is connected. The system technician dispatched to 
investigate this problem should take a spare CI card in case the CI card 
caused the failure. If you are NOT ON-SITE, use the following procedure: 
1. Look for DS1-BD (DS1 Interface Circuit Pack) errors using the display 
error command. Refer to the DS1-BD Maintenance documentation for 
recommended strategy to resolve any DS1-BD errors found.
2. If there are no DS1-BD errors OR after resolving all DS1-BD errors, issue 
the test synchronization r 4 command to determine if the alarm is still 
present. If all repetitions of the tests pass, then the alarm no longer exists. 
Otherwise, the system technician should be dispatched with a spare CI 
card to use the following instructions on-site. (
continued)