Maintenance Object Repair Procedures 
9-1545
STRAT-3 (Stratum 3 Clock) 
9
1
FAIL
(
continued) 
If you are ON-SITE, use the following procedure: 
1. Look for a red LED on CI card A (i.e., the left CI card). If there is a red LED, 
then replace the CI card, if a spare is available. If no spare CI is available 
on-site, proceed to Step 3. If after replacing the CI card, the red LED on 
the new CI card lights also, then proceed to Step 3. 
2. If a spare CI card is available, replace the suspect CI card. Otherwise, 
issue the test synchronization r 4 command to clear the alarm. If any test 
repetitions fail, then follow the procedure for those failures. 
3. Look for DS1-BD (DS1 Interface Circuit Pack) errors using the display 
error command. Refer to the DS1-BD Maintenance documentation for 
recommended strategy to resolve any DS1-BD errors found. If there are no 
DS1-BD errors, then proceed to Step 5. 
4. After all DS1-BD errors have been resolved, then determine if the alarm 
still exists by issuing the test synchronization r 4 command to clear the 
alarm. If any test repetitions fail, then follow the procedure for those 
failures. 
5. Check the DS1 reference A connections to the Stratum 3 clock.
6. Determine if the alarm still exists by issuing the test synchronization r 4 
command to clear the alarm. If any test repetitions fail, then follow the 
procedure for those failures.
2
FAIL
One power supply failed. This error only occurs when the Stratum 3 clock has 
two power supplies, and one of them has failed. However, the clock can 
function with one power supply. 
1. Locate the failed power supply by looking for a power supply with a red 
LED and replace it. The power supply is located under the Stratum 3 clock 
carrier.
2. Determine if the alarm still exists by issuing the test synchronization r 4 
command to clear the alarm. If any test repetitions fail, then follow the 
procedures for those test failures.
4
FAIL
One clock unit failed. 
1. Look at the Stratum 3 cabinet for a red LED on a circuit card marked 
‘‘ST3.’’ Replace the card. 
2. Determine if the alarm still exists by issuing the test synchronization r 4 
to clear the alarm. If any test repetitions fail, then follow the procedures for 
those failures.
Table 9-588.
TEST #161 Looparound Test  — Continued
Error 
Code
Test 
Result
Description/ Recommendation
Continued on next page