Hitachi SJ300-037HFE Manuel D’Utilisation

Page de 289
Analog Input Operation
Oper
ations
a
nd Moni
tor
ing
4–60
The following tables show the available analog input settings. Parameters A006, A005, and 
input terminal [AT] determine the External Frequency Command input terminals that are avail-
able and how they function. The Trim Frequency input [O2]—[L] is available (when check 
marked) for some settings. Other settings make the reverse direction (in addition to forward) 
available for bipolar input settings (when check marked). A bipolar input responds to positive 
input voltages with a forward motor rotation, and to negative input voltages with reverse motor 
rotation.
The table below applies when the [AT] input function is not assigned to any intelligent input 
terminal. The A005 setting, normally used in conjunction with an [AT] input, is ignored.
CAUTION: Whenever the [AT] input function is not assigned to any input terminal and 
reverse rotation is not desired or is unsafe, be sure to set A006 = 01. This setting makes the 
[O2] input unipolar only.
A006
A005
[AT]
External Frequency 
Command Input
Trim Frequency 
Command Input
Reverse avail.
(bipolar input)
00
00
OFF
[O]
ON
[OI]
01
OFF
[O]
ON
[O2]
01
00
Example 
1
OFF
[O]
[O2]
ON
[OI]
[O2]
01
OFF
[O]
[O2]
ON
[O2]
02
00
Example 
2
OFF
[O]
[O2]
ON
[OI]
[O2]
01
OFF
[O]
[O2]
ON
[O2
A006
A005
[AT]
External Frequency 
Command Input
Trim Frequency 
Command Input
Reverse avail.
(bipolar input)
00
(not 
assigned 
to any 
input 
terminal)
[O2]
01
Summation of
[O] and [OI]
[O2]
02
Summation of
[O] and [OI]
[O2]