Emerson 20/20 Manuel D’Utilisation

Page de 120
6 – 8
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153
operator consult PID tuning guides available from 
many different source before attempting to tune this 
PID.
Liquid inj. Setpoint 1:
•  Setpoint at which the liquid solenoid will activate if in 
solenoid control or if the setting for the control vari-
able for the PID is in liquid motorized value control.
Liquid inj. Setpoint 2:
•  Not yet available
Oil Sep. Temp. Override:
• Defi nes the temperature the oil must reach before the 
liquid injection solenoid is allowed to be activated.
P = Proportional (Gain):
•  Used to adjust the positioning valve in direct propor-
tion to the difference between the control setpoint 
and the discharge temperature (SetPt - DT = error). 
The proportional term is a unit-less quantity and is 
used for coarse adjustment. This setpoint should be 
set to the lowest value that gives adequate response 
to the control system. Increasing the proportional 
setting increases the control system’s sensitivity to 
small discharge temperature fl uctuations and the 
tendency to hunt.
I = Integral (reset):
•  This parameter integrates the error over time, to ac-
count for a small error that has persisted for a long 
time. This quantity is used for fi ne adjustment. This 
setpoint is used to smooth out discharge tempera-
ture variations. This setpoint should be set high 
enough to prevent hunting but not too high or it will 
cause control system overshoot.
D = Derivative (rate):
•  This parameter accounts for how fast the error is 
changing, positively or negatively.
Minimum Valve Open %:
•  When enabled, this is the valve position used when-
ever the control variable drops below Liquid inj. 
Setpoint 1. Use only if the compressor is tripping off 
for low oil temperature due to large overshoots and 
all other tuning methods have failed.
Avg. with Oil Manifold Temperature:
•  When enabled, averages the Oil manifold tempera-
ture and the discharge temperature. This creates 
a more stable control variable and should result in 
more stable control.
Section 6 • Compressor Control