7 – 1
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153
Overview
The Alarms and Trips screen allows the operator to view 
and adjust settings for compressor safety and alarm set-
tings, see Figure 7-1. Alarms and Trips Screen. Vission 
20/20 uses Alarms as a way to notify the operator of 
running parameters that if left unchecked could result 
in the compressor shutting down due to a trip. Trips are 
the conditions that exceed the safety limits of the com-
pressor or refrigeration system and stops the compres-
sor. Trips are always displayed as a red banner and alarms 
are yellow banners on the top and bottoms status bars. 
Alarms and trip conditions are also logged to provide 
an operational history for the operator. Both alarms 
and trips will be logged in the event list accessible from 
the menu screen. Trips also trigger the input/output 
screen to take a snapshot of all input and output values 
as freeze screen. The freeze screens are available as left 
side tabs in the input/output screens and are very useful 
as a troubleshooting tool for the operator. 
Alarms and Trips Setpoints
Low Suction Pressure (Alarm & Trip):
•  This is the low suction pressure safety. This safety 
is active in both temperature and pressure control 
modes. An alarm or trip will be activated if the suc-
tion pressure falls below the setpoint values.
High Discharge Pressure (Alarm & Trip):
•  This is the high discharge pressure safety. The alarm 
or trip will be activated if the discharge pressure rises 
above the setpoint value.
High Process Temperature (Alarm only)
•  This alarm is active when the process temperature 
is at or above the setpoint value. There is no trip 
setpoint.
Low Process Temperature (Alarm & Trip):
•  This is the low control temperature safety. This safety 
is active when process temperature control has been 
Figure 7-1. Alarms and Trips Screen
Section 7 • Alarms and Trips