Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153
Status Symbols:
•  Status symbols shows status of Slave compressors on 
the sequencing table. Please see Application Notes 
for more details.
Section 10 • Compressor Sequencing
Machine Stop Time:
•  Machine Stop timer shows the time in sec that the 
Master Compressor will hold before stopping slave 
compressor once (Stop ) decision is taken.
Refresh:
•  Compressor Sequencing table is automatically re-
freshed every 1 minute. Pressing “Refresh” button 
refreshes the status of the Compressor Sequencing 
table on Master Compressor.
NOTE
Before Confi guring Sequencing table on Master 
Compressor, log on to slave compressors one by 
one and enable sequencing in slave mode, put slave 
in remote mode. Then log on to Master Compressor 
and wait till all slaves show up their names under 
equipment List.
Slave Compressor is detected but is not confi gured in the sequencing table.
Default, If slave Compressor is not present.
Slave Compressor is confi gured in sequencing table but is not confi gured in “Remote” mode.
Slave Compressor confi gured in sequencing table and is in ready to run state.
Slave Compressor is running with Alarm condition.
Slave Compressor stopped due to Error Condition.
Slave Compressor running at maximum capacity without any error.
Slave Compressor under active control of Master Compressor
Slave Compressor running into its stop timer, will be stopped.