Section 10 • Compressor Sequencing
Overview
Compressor sequencing screen is where more than one 
Vission 20/20 panels can be sequenced in network using 
Modbus TCP. These settings defi ne how the master com-
pressor should control sequenced Vission 20/20 panels. 
This feature is enabled from the Confi guration Screen, 
see Figure 10-1. Compressor Sequencing Screen.
Compressor Sequencing:
•  Enables Compressor Sequencing. Uncheck the box to 
disable compressor sequencing. 
Master:
•  Enables Compressor Sequencing in Master Mode. 
Slave:
•  Enables Compressor Sequencing in Slave Mode.
Compressor Name:
• Defi nes Unique name of a Compressor / Vission 
20/20 Panel on sequenced network.
Pressure Control Setpoints
Compressor Sequencing screen defi nes settings those 
are used by master compressor for sequencing.
Load Rate 2 offset (outer):
• Defi nes the outer pressure/temp setpoint offset to 
monitor compressor load. If Suction pressure / pro-
cess temperature surpasses Load Rate 1 offset and 
goes beyond Load Rate 2 setpoint offset then se-
quencing decisions are made according to Load Rate 
2 timer.
Load Rate 1 offset (inner):
• Defi nes the inner pressure/temp setpoint offset to 
Figure 10-1. Compressor Sequencing Screen