Emerson VISSION 20/20 Manuel D’Utilisation

Page de 80
22
OIL MANIFOLD PRESSURE - Default signal is 4-20Ma.  Oil manifold pressure transducer range and calibration is set 
in the calibration screen.
VRS OIL INJECTION PRESSURE – Default signal is 4-20Ma.  VRS oil injection pressure transducer range and calibra-
tion is set in the calibration screen.
% SLIDE VALVE POSITION – Reads the 0-5 volt signal back from the slide position motor actuator to indicate cur-
rent slide valve position.
% VOLUME POSITION – Reads the 0-5 volt signal back from the slide volume motor actuator to indicate current 
volume position.
SUCTION TEMPERATURE – Default signal is RTD.  Suction temperature calibration is set in the calibration screen.
DISCHARGE TEMPERATURE – Default signal is RTD.  Discharge temperature calibration is set in the calibration 
screen.
OIL SEPARATOR TEMPERATURE – Default signal is RTD.  Oil separator temperature calibration is set in the calibra-
tion screen.
OIL MANIFOLD TEMPERATURE – Default signal is RTD.  Oil manifold temperature calibration is set in the calibra-
tion screen.
PROCESS TEMPERATURE – Default signal is RTD.  Process temperature calibration is set in the calibration screen.
LEVEL PROBE (COOL COMPRESSION) – Default signal is 4-20mA.  Measures separator level.  Level probe calibration 
is set in the calibration screen.
CONDENSER PRESSURE – Default signal is 4-20Ma.  Condenser pressure transducer range and calibration is set in 
the calibration screen.
REMOTE CAPHOLD – Default signal is 4-20Ma.  Active in “Direct I/O” mode.  Adjusts the capacity of the compres-
sor from 0-100%, proportional to the 4-20mA signal. 
ECONOMIZER PRESSURE – Default signal is 4-20Ma.  Economizer pressure transducer range and calibration is set 
in the calibration screen.
CHILLER IN TEMPERATURE – Default signal is RTD.  Chiller inlet temperature calibration is set in the calibration 
screen.
MOTOR WINDING TEMPERATURE #1 thru #3 - Default signal is RTD.  One RTD is installed in each of the three mo-
tor windings to monitor motor winding temperature.
AUXILIARY #1 thru #7 – Flexible analog inputs that can be configured to control, alarm or trip.
BEARING TEMP #1 thru #4 - Default signal is RTD.  Monitors bearing temperatures in both the compressor and 
motor.