Emerson VISSION 20/20 Manuel D’Utilisation

Page de 80
23
BOARD
   I/O # 
DESCRIPTION   
 
 
 
 
TYPE
#
10 
Compressor VFD 
 
 
 
 
4-20 mA
10 
Condenser VFD   
 
 
 
 
4-20 mA
10 
% Slide Valve Position 
 
 
 
 
4-20 mA
10 
Motorized Valve
 (Cool Compression or Liquid Injection), V+
 
4-20 mA
10 
Profile Cooler VFD (Profile only)   
 
 
4-20 mA
10 
 
10 
 
10 
 
COMPRESSOR VFD – 4-20mA output to control compressor motor speed with a Variable Frequency Drive (VFD). 
CONDENSER VFD – 4-20mA output to control one condenser fan which is interleaved between the remaining 
condenser steps for smoother control.
% SLIDE VALVE POSITION – 4-20mA signal that transmits the slide valve position for remote monitoring.
MOTORIZED VALVE (V+) – for a cool compression compressor, this 4-20ma signal controls a motorized valve to 
regulate the liquid refrigerant level in the oil separator.  For a liquid injection application on a standard single 
screw, this 4-20ma signal controls a motorized valve to regulate the liquid refrigerant injected into the compres-
sor for oil cooling purposes.
PROFILE VFD – for a profile unit compressor, this signal controls the aftercooler fan speed which provides oil cool-
ing.
Analog Outputs