I. DELIVERY 
INSPECTION
Vilter screw compressor components are thor-
oughly inspected at the factory, assuring the 
shipment of a mechanically perfect piece of equip-
ment.  Damage can occur in shipment, however.  
For this reason, the units should be thoroughly 
inspected upon arrival.  Any damage noted should 
be reported immediately to the transportation 
company.  This way, an authorized agent can ex-
amine the unit, determine the extent of damage 
and take necessary steps to rectify the claim with 
no serious or costly delays.  At the same time, 
the local Vilter representative or the home offi ce 
should be notifi ed of any claim made.
TABLE 1. 
UNIT WEIGHTS (LBS)*
MODEL STANDARD 
 
ECON-O- 
   MIZER
VSM 71 
2,750 
2,750
VSM 91 
2,750 
2,750
VSM 101 
2,750 
2,750
VSM 151 
2,750 
2,750
VSM 181 
2,750 
2,750
VSM 201 
2,750 
2,750
VSM 301 
2,850 
2,850
VSM 361 
2,850 
2,850
VSM 401 
2,850 
2,850
VSM 501 
4,000 
4,000
VSM 601 
4,500 
4,500
VSM 701 
5,000 
5,000
VSS 451 
4,000 
4,000
VSS 601 
4,500 
4,500
VSS 751 
5,300 
5,300
VSS 901 
5,300 
5,300
VSS 1051 
6,600 
6,600
VSS 1201 
6,700 
6,700
VSS 1301 
6,750 
6,750
VSS 1501 
10,010 
10,010
VSS 1801 
10,010 
10,010
VSS 1551 
11,000 
11,000
VSS 1851 
11,000 
11,000
VSS 2101 
11,000 
11,000
* Does not include motor.
II. FOUNDATIONS
Vilter single screw compressor units are basi-
cally vibration free machines, therefore, no 
elaborate foundations are necessary. The fl oor 
or foundation upon which the unit will be placed 
should be designed to support the entire op-
erating weight of the unit. See Table 1 for unit 
weights. See Foundation, page 12, for additional  
foundation instructions.
III. 
LOCATING UNIT - DRIVE    
 
 COUPLING 
ALIGNMENT
The single screw compressor units are shipped 
with all major components mounted on struc-
tural steel.  Place the entire unit on the fl oor 
on a concrete pad and securely bolt in place.  
Review local codes and ASHRAE Safety Code for 
Mechanical Refrigeration.  Bolt holes are located 
in the unit’s mounting feet.  When locating the 
unit, provide adequate space for service work.  
When the compressor unit is in place on the con-
crete pad, check both lengthwise and crosswise 
to assure it is level.  Use shims and wedges as 
needed under the mounting feet to adjust the 
level of the unit.
On single screw units, the motor and compres-
sor have been roughly aligned at the factory.  
The coupling center section was shipped loose 
to allow a check of proper electrical phasing, 
direction of rotation of the motor and final 
coupling alignment.  The dial indicator align-
ment method is recommended.  Final alignment 
should be within 0.004 inches total indicator 
reading in all direction for the VSS models and 
0.010 inches for the VSM models.
III. SYSTEM 
PIPING
Refer to the ANSI/ASME B31.5 Code for Refrig-
eration Piping.  All compressor oil supply and oil 
return piping has been completed at the factory.  
The necessary connections to be made to the 
screw compressor unit will vary depending on 
the type of oil cooling method purchased.  Main 
line refrigerant suction and discharge connec-
tions are always necessary.