Operation
4.  Manually open the oil isolating valve at the oil 
separator outlet connection.
5.  Open the isolating valve(s) before and after the 
oil filter housings.
6.  Manually open the stop valve on the oil bleed 
return line from the element section and open 
the expansion valve 1/2 of a turn.
FIGURE 6.
OIL SEPARATOR BLEED LINE
 
NOTE:
The purpose of the oil bleed return assembly is to 
collect any oil that passes through the oil separat-
ing element and returns that oil to the compres-
sor.  The hand expansion valve should be adjusted 
to prevent an oil level from forming in the sight 
glass when the compressor is at 100% capacity.  
Generally 1/2 to 1 turn open is satisfactory.
7.   Open 1/4” high pressure gas line valve piped to 
oil injection line just enough to quiet compres-
sor at 100% capacity.
C. Compressor Pre Start-Up Check  List
Before proceeding with actual starting of the 
compressor, the items listed on the “Pre Start-Up 
Check List” must be verified.  Time and money will 
be saved before the Vilter start-up technician ar-
rives.  (See next page.)
3. Suction Pressure
Low suction pressure cutout stops the compres-
sor unit when the suction pressure drops below 
the setpoint.
4. Oil Filter Differential
High oil filter differential cutout stops the com-
pressor unit when the difference between the 
outlet and inlet of the filter exceeds the setpoint.
5. Oil Temperature
The oil temperature cutout stops the compres-
sor unit when the oil temperature is too high 
or too low.
6. Discharge Temperature
The high discharge temperature cutout stops 
the compressor unit when the discharge tem-
perature exceeds the setpoint.
INITIAL START-UP
A. Setting of Controls
(Refer to the appropriate microprocessor manual  
for a list of initial settings.)
B. Valve Settings
1.  The suction line uses separate stop and check 
valves. Ensure the suction stop valve is open 
prior to starting.
2.  The ¼” suction equalization valve should be 
closed during operation.  The valve enables the 
unit to slowly equalize to low side pressure dur-
ing off periods. This valve must be adjusted to 
minimize oil loss when compressor stops.
3.  The discharge line uses separate stop and check 
valves.  Ensure the discharge valve is open prior 
to starting.
 
SG
HAND EXPANSION
VALVE
TO COMPRESSOR
STRAINER
SIGHT
GLASS
VALVE
CHECK