4.1.5. 
Map Descriptor Example 2 – Port has Sub-Ports. 
This Map Descriptor is used to store messages from ‘Panel2’ if they meet the following criteria 
 
 
Panel Number  
= Node ‘Panel2’s Node_ID 
Board  
= 1 
Loop   
=  2 
Port-Type  
= Inputs 
Port           
= 20 
Data_Type = 
Alarms 
Sub-Port-Type = 
Output 
Sub-Port-
Number 
= 1 
 
Map_Descriptor_Name, 
Data_Array_Name, 
Data_Array_Offset, 
Function, 
Node_Name, 
Board, 
Loop, 
Data_Type, 
Port-Type, 
Address, 
Length, 
Sub-Port-Type 
Sub-Port 
P2B3L4_ia, 
P2B3L4_iA , 
0, 
Passive_Client , 
Panel2 , 
1, 
2, 
Alarms, 
Input, 
0, 
1, 
Output