Omron C200HE Manuel D’Utilisation

Page de 564
402
7-2-9
3-word Monitor
To monitor three consecutive words together, specify the lowest numbered
word, press MONTR, and then press EXT to display the data contents of the
specified word and the two words that follow it.
A CLR entry changes the Three-word Monitor operation to a single-word display.
Key Sequence
Single-word monitor in progress
00000
00000
CHANNEL  DM 0000
D0000
 89AB
D0002D0001D0000
 0123 4567 89AB
D0003D0002D0001
 ABCD 0123 4567
D0004D0003D0002
 EF00 ABCD 0123
D0005D0004D0003
 1111 EF00 ABCD
D0004D0003D0002
 EF00 ABCD 0123
D0002
 0123
Specify the first of the 3 words
you want to monitor.
Press the Up and Down Arrow
keys to change word addresses.
7-2-10
3-word Data Modification
This operation changes the contents of a word during the 3-Word Monitor opera-
tion. The blinking square indicates where the data can be changed. After the
new data value is keyed in, pressing WRITE causes the original data to be over-
written with the new data. If CLR is pressed before WRITE, the change operation
will be cancelled and the previous 3-word Monitor operation will resume.
This operation cannot be used to change SR 253 through SR 255. Only those
words displayed on the 3-word Monitor display can be changed.
Key Sequence
3 words currently
displayed
[ Data ]
Example
Programming Console Operations
Section 7-2