Siemens LU01 Manuel D’Utilisation

Page de 114
7ML19985BE02
SITRANS LU01 – INSTRUCTION MANUAL
Page 7
mm
mmm
Spec
if
icat
ions
Transducer 
Compatible Models
• STH and Echomax
®
 series 
• Refer to the associated instruction manual. 
Options 
Temperature Sensor
• TS-3 
SmartLinx Modules
• Supported protocols:  PROFIBUS DP
Allen-Bradley®
1
 Remote I/O
Modbus® RTU
DeviceNet
TM
Dolphin Plus
• Windows
®
-compatible configuration software connected to the unit via infrared 
Comverter link
Refer to associated product documentation.
Cable
Transducer
• RG-62 A/U (or equivalent), 365 m (1,200 ft) max. 
See transducer instructions for short extensions (in grounded metal conduit, separate 
from other wiring) 
mA Output
• Belden 8760, shielded / twisted pair, 18 AWG (0.75 mm
2
) or equivalent or Belden 9552, 
shielded / two twisted pair, 18 AWG (0.75 mm2)
• maximum separation 1,500 m (5,000 ft) 
Synchronisation
• Belden 8760, shielded / twisted pair, 18 AWG (0.75 mm
2
) or equivalent
Relays
• No shielded cable necessary 
Temperature sensor
• Belden 8760 shielded / twisted pair, 18 AWG (0.75 mm
2
) or equivalent
• 365 m (1,200 ft) per TS-3 maximum
RJ11 Link
• No shielded cable necessary 
• maximum length 3 m (10 ft)