Installation 
Installation shall only be performed by qualified personnel, and in accordance with local 
governing regulations. 
The following procedure applies to all SITRANS LU01 level monitor installations. See 
Application Examples on page 89 for additional installation requirements. Also, refer to 
the instruction manuals of all other equipment connected to the SITRANS LU01 for 
additional installation instructions. 
SITRANS LU01 
Location 
Recommended
Ambient temperature is always within -20 to 50 °C (-5 to 122 °F)
SITRANS LU01 display window is at shoulder level, unless most interaction is 
through a SCADA system
Easy access for hand programmer is provided 
Cable length requirements are minimal
Mounting surface is free from vibration
Leave sufficient room to swing unit lid open and have clear access.
A place for a laptop computer is provided for on-site Dolphin Plus configuration
Avoid 
Exposure to direct sunlight. (Provide a sun shield to avoid direct sunlight.) 
Proximity to high voltage/current runs, contacts, SCR or variable frequency motor 
speed controllers
Cable/Conduit Entry Requirements 
Enclosure cable/conduit entries may be required for: 
Transducers 
TS-3 temperature sensor (if used) 
mA output (if used) 
Relays (if used) 
Synchronization (see Interconnection/Level System Synchronization) 
Power 
Communications:
 
SmartLinx, RS-485, RS-232, bipolar.
Note: 
Transducer cables must be run in a grounded metal conduit, separate from 
other wiring, (except TS-3 temperature sensor wiring, if applicable).