SITRANS LU01 – INSTRUCTION MANUAL
Page 91
mm
mmm
Te
c
hnical Ref
e
re
nce
Parameter Settings for Point # 1
With process control equipment disabled, enter the RUN mode to monitor system 
performance and alarm programming. Otherwise, perform a Reading Measurement 
simulation (P920). 
When satisfied with system performance and programming: 
connect a high alarm indicator to Relay #1 (see P100 = 4). 
connect a low alarm indicator to Relay #2. 
connect a high high alarm indicator and filling equipment stop/start control to 
Relay #3. 
connect a low low alarm indicator to Relay # 4. 
(Note that relays are de-energized in power off and alarm conditions). 
For cement applications (or any very dusty dry solids), measurement difficulties during 
vessel filling are common. For this example (assume the maximum filling rate), failsafe 
operates as follows: 
e.g.
Number
Description
Instructions
P001
Operation
Enter "1" for 
level
P002
Material
Enter "2" for 
solid
P003
Measurement Response
Enter "1" for 
slow
 (0.1 m/min). 
P004
Transducer
Enter "107" for 
XLT-30
P005
Units
No entry required, (preset for 
metres
). 
P006
Empty
Enter "30" for transducer face to Empty equals 
30.00 
metres
P007
Span
No entry required, (preset to 
29.01 metres
). 
P070
Failsafe Timer
Enter "2" for failsafe activation after 
2 minutes
 without 
a valid echo. 
P071
Failsafe Material Level
Enter "HI" for 
advance to Span on "LOE"
P072
Failsafe Advance
No entry required. (preset to 
restricted
). 
P100
Relay Set Up
Enter "4" for 
High, Low, High High, and Low Low
 alarm 
relays. 
P101
High
 Alarm
Enter "25" for 
High
 Alarm at 
25.00 m
P102
Low
 Alarm
Enter "10" for 
Low
 Alarm at 
10.00 m
P103
High
 
High
 Alarm
Enter "27" for 
High
 
High
 Alarm at 
27.00 m
P104
Low
 
Low
 Alarm
Enter "5" for 
Low
 
Low
 Alarm at 
5.000 m
09:15 am
Echo lost at 6.00 m, low alarm is still on, failsafe coundown begins
09:17 am
Failsafe activated,
actual level = 6.16 m,
reported level = 6.00 m.
09:57 am
Low alarm off,
actual level = 9.36 m,
reported level = 10.00 m.
12:27 am
High alarm on,
actual level = 21.36 m,
reported level = 25.00 m.
12:47 am
Infeed stopped,
actual level = 22.96 m,
reported level = 27.00 m.