Siemens LU01 Manuel D’Utilisation

Page de 114
7ML19985BE02
SITRANS LU01 – INSTRUCTION MANUAL
Page 89
mm
mmm
Te
c
hnical Ref
e
re
nce
The Process Speed setting automatically adjusts various parameters affecting the 
SITRANS LU01 response to material level changes as in the table that follows.
* Scan Delay (P727) is globally set for all Point Numbers to the value associated with the 
fastest Measurement Response (P003) selected for Point Number 1or 2. 
Application Examples 
The following examples describe the use of SITRANS LU01 programmable features, to 
meet the needs of specific process measurement requirements. 
It is highly unlikely that your specific installation will match one of these examples 
exactly. 
However, by reviewing the example (or combination of examples) that matches your 
installation best, the relationship between SITRANS LU01 features and process 
measurement requirements may be more easily recognized.
Parameter
Values Dependent on Measurement Response 
(P003) Value
#
Name (Units)
1(slow)
2(medium) 3(fast)
4(surge)
(5imm.)
P070 Failsafe Timer (min)
100
10
1
0.1
0
P700 Max Fill Rate (m/min)
0.1
1
10
100
1000
P701 Max Empty Rate (m/min)
0.1
1
10
100
1000
P702 Filling Indicator (m/min)
0.01
0.1
1
10
100
P703 Emptying Indicator (m/min) 0.01
0.1
1
10
100
P704 Rate Filter (option)
4
3
2
2
2
P710 Fuzz Filter (% of P007)
100
50
10
1
0
P711 Echo Lock (option)
1 or 2 (dependent on Material (P002)
P713 Echo Lock Window
(dependent on P701/P702 and time since last valid measure-
ment)
P728 Shot Delay (s)
0.5
0.5
0.5
0.2
0.1
P803 Shot/Pulse Mode (option)
2
2
2
1
1
P841 Long Shot Number (qty)
10
5
2
1
1
Example #
Description
1
Level (or Material Volume) Measurement for a single vessel. 
2
Space (or Remaining Vessel Capacity) Measurement for a single vessel.