- 8 - 
2.2. DeviceNet indicator 
The DEV002Z 
option
 has a two-color (red and green) LED as a means of indicating 
the MNS (module/network status), which works basically in accordance with 
DeviceNet specifications.   
 
LED 
Status 
Item displayed 
Off 
Not Powered/Not On–line 
Device is not on-line. 
- The DEV002Z has not completed the Dup_MAC_ID test yet. 
- The DEV002Z may not be powered. 
Lights 
green. 
Device Operational AND 
 On–line, Connected 
The DEV002Z is operating in a normal condition and the DEV002Z 
is on-line with connections in the established state. 
Flashes 
green. 
Device Operational AND 
  On–line, Not Connected
 
or
 
Device On–line AND 
  Device needs commissioning 
The DEV002Z is operating in a normal condition and the DEV002Z 
is on-line with no connections in the established state. 
- The DEV002Z has passed the Dup_MAC_ID test, is on-line, but 
has no established connections to other nodes.
 
- Configuration missing, incomplete or incorrect. 
Flashes 
red.   
Minor Fault and/or 
 Connection Time–Out 
Recoverable fault and/or one or more I/O Connections are in the
 
Timed-Out state. 
Lights red.   
Critical Fault or 
  Critical Link Failure 
The DEV002Z has an unrecoverable fault; may need replacing.
 
Failed communication device. The DEV002Z has detected an error 
that has rendered it incapable of communicating on the network 
(Duplicate MAC ID, or Bus-off). 
Flashes 
red and 
green 
alternately.   
Communication Faulted and 
  Received an Identify Comm 
Fault Request - Long Protocol 
A specific Communication Faulted device. The DEV002Z has 
detected a Network Access error and is in the Communication 
Faulted state.   
The DEV002Z has subsequently received and accepted an Identify 
Communication Faulted Request - Long Protocol message.