National Instruments SCC-AI05 Manuel D’Utilisation

Page de 18
© National Instruments Corporation
5
SCC-AI Series Isolated Analog Input Modules
Connecting the Input Signals
The SCC-AIXX has a fixed screw-terminal receptacle and a removable 
screw-terminal block, as shown in Figure 1-2.
 
Figure 1-2.  SCC-AIXX Two-Part Screw-Terminal System
After you install the SCC-AIXX, connect the input signals to the removable 
screw-terminal block of the module.
1.
Remove power from the signal lines.
2.
Strip 7 mm of insulation from the ends of the signal wires.
3.
Insert the wires into the screw terminals.
4.
Tighten the screws to 0.5 to 0.6 N · m (4.4 to 5.3 lb - in.) of torque.
Each screw terminal is labeled by pin number <1..4>. Pins 1 and 2 form a 
channel routed to E Series DAQ device channel X
+8, and pins 3 and 4 form 
a channel routed to the E Series DAQ device channel X, where X is 0 to 7 
depending on the socket where you plug in the module. The SCC-AIXX 
provides channel-to-ground and module-to-module isolation only. It does 
not provide isolation between the two channels of the SCC-AIXX. Because 
both channels must have the same reference voltage, pins 1 and 3 are 
connected together internally. Figure 1-3 shows the SCC-AIXX signal 
connections.
1
SCC Screw-Terminal Receptacle
2
Removable Screw-Terminal Block
3
2
1
4
1
2