3.1.4  Saving the settings 
Apart from some network parameters, most setting are immediately active. However, the adapter will 
revert to the last save settings at reboot. Therefore, in order to permanently modify the SNMP/Web 
adapter setting, remember to save the configuration after every change. 
 
 
3.2  NAVIGATION BAR 
The top navigation bar features the following items: 
•  Home: is the web server home page, showing basic information on the system and the network 
settings 
•  UPS: access to the UPS section, for UPS monitor, control and configuration 
•  System: adapter configuration (network settings, time management, etc.) 
•  SMTP: configuration and control of the e-mail notification functionality 
•  SNMP: configuration of the SNMP Agent and trap notification 
•  Log: UPS log and System log  
•  Utility: various utility applications (e.g. DNS lookup, media technology selection and verification) 
and service enable page 
•  Save: save the current settings and/or force a reboot 
•  User: user management  
 
The following paragraphs will detail each single section 
 
 
3.3  UPS SECTION 
The UPS pages can be split in two different sections: UPS monitoring and UPS control. 
The IdentificationBatteryStatus, Alarms and PMAD pages are part of the UPS monitoring section. These 
pages allow to remotely access the UPS status and measurements. Please note that each specific UPS 
model may implement a subset of the available measurement – data not available for the specific UPS 
is marked as N/A
The  Test,  Control and Config pages are part of the UPS control sections. Once again, the supported 
command and configuration options depend on the specific UPS model. Unsupported option are 
marked as N/A and cannot be set. It must be stressed that some of the command will affect the UPS 
and may cause alarms or UPS malfunction and eventually switch off the UPS (as is the case with the 
shutdown command).  
Caution! Make sure you fully understand the effect on the UPS and on the load before injecting any 
command or altering any configuration parameter.  
 
In a 3-ph parallel UPS system, the SNMP/Web adapter presents the readings from every single UPS and 
from the overall system. 
 
 
3.3.1  UPS Identification page 
The UPS Identification page shows the following information: 
•  UPS Manufacturer 
•  UPS Model 
•  Serial Number 
•  Software Version – the version of the main UPS control board firmware 
•  Protocol Version – the version of the serial protocol used to communicate with the UPS 
•  UPS Attached Devices – identification of the devices attached to the UPS output (as set by the 
administrator). 
Modifications reserved 
Page 27/58 
OPM_CNT_SNM_BAS_CRD_1GB_V012.doc 
Operating Manual SNMP/Web Adapter