3.3.3  UPS Status page 
The UPS status page shows the following information for each of the input / output / bypass lines. 
 
Parameter Name 
Description 
Frequency 
Line frequency (in Hertz) 
Voltage 
Line RMS voltage (in Volts) 
Line RMS current  (in Amperes) 
Current  
Power / True Power  
Line True Power (in Watt) 
Load % 
The power capacity presently being used (percentage) 
[Output only] 
Volt min  
Lowest input voltage in the present time-period (in Volts) 
[Input only] 
Lowest input voltage in the present time-period (in Volts) 
[Input only] 
Volt max 
 
Also the following information is presented: 
 
Parameter Name 
Description 
Input Line Bads 
Number of times the mains input went out-of-tolerance since UPS start-up 
The present source of the output power  
Output Source 
Note: none means there is no output power 
 
Finally, a 3-ph system featuring the PMAD functionality will also show the following: 
 
Parameter Name 
Description 
The present output power factor. A positive value indicates an inductive load; 
while a negative value indicateS a capacitive load. 
Power factor 
Note: the power factor cannot be reliably determined in low load conditions. In 
this case, the value will not be available (N/A) 
The output peak current  
Peak current 
Share current 
In a parallel system ideally all the UPS are requested to contribute to the load 
with the same amount of current, i.e. with no current share. The current share 
occurs when an UPS exchanges some current with another UPS, so that this 
current component doesn't feed the load.  
The PMAD functionality detects the amount of share currents in a parallel 
system. Obviously, single system do not provide this functionality and will show 
this value as not available (N/A). 
 
3.3.4  UPS Alarm page 
This page presents the UPS active alarms (if any) with an indication of the time elapsed since the 
activation (in seconds). Once again, the supported alarms depend on the specific UPS model. 
 
For the meaning of each specific alarm refer to the relevant UPS documentation. 
 
3.3.5  UPS PMAD page (3-ph version ONLY) 
This page presents diagnostic related readings from UPSs implementing the PMAD (Preventive 
Maintenance and Advanced Diagnostic) functionality. These include the following: 
 
Parameter Name 
Description 
The remaining time before a check of the specific devices / system  is required 
Life Time 
Count of failures and transients on mains input and bypass 
Mains Statistics 
Bus Communication 
Qty of UPSs: Number of UPSs as currently seen in the parallel system.  
(The reset button forces a refresh of the count and the display) 
Channel table: The table shows the actual communication status over the two 
redundant buses between the unit currently selected (in green bold) and other 
units. 