10.6  TROUBLESHOOTING E-MAIL NOTIFICATION (SMTP)  
When e-mail notification via SMTP is configured and enabled, the SNMP/Web adapter will notify the 
selected recipients upon UPS alarm activation / deactivation. If problems are experienced with this 
functionality, follow the flowchart below to identify the root-cause of the problem and implement 
proper corrective actions.  
Please note that proper configuration of the SNMP/Web adapter and the SMTP server set-up and 
configuration are responsibility of the user. This section aims to give basic troubleshooting guidance.  
For details on SMTP protocol refer to RFC 821, RFC 1123 and RFC 2821. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
N
N
E-mail notification
E-mail OK
Check SMTP server operation
telnet my.smtp.server smtp
Server OK  ?
Resolve SMTP 
server issues
Y
N
OK
Y
N
Ping SMTP server
from the adapter
Ping OK ?
Y
Send test e-mail
GEDE>sendemail test
Email OK ?
Verify TCP/IP settings
(*)
Y
Check adapter / 
SNMP server 
configuration (**)
OK
N
N
E-mail notification
E-mail OK
Check SMTP server operation
telnet my.smtp.server smtp
Server OK  ?
Resolve SMTP 
server issues
Y
N
OK
Y
N
Ping SMTP server
from the adapter
Ping OK ?
Y
Send test e-mail
GEDE>sendemail test
Email OK ?
Verify TCP/IP settings
(*)
Y
Check adapter / 
SNMP server 
configuration (**)
OK
 
 
(*)If the adapter and the SMTP server belong to different subnets check the gateway settings. 
 
(**) Particularly: 
•  If the SMTP server supports logging, enable the log functionality. Server error messages may 
give useful hints on the nature of the problem 
•  Check the SNMP/Web adapter hostname (must be a valid domain name), SMTP sender-name 
and e-mail recipient (both must be valid e-mail addresses) 
•  If the SMTP server requires authentication, verify the account settings on the SNMP/Web 
adapter. 
 
With reference to Authentication, the embedded e-mail client only supports the CRAM-MD5 and LOGIN 
mechanisms. Make sure the e-mail server supports at least one of these mechanisms. 
 
 