Emerson FPC Manuel D’Utilisation

Page de 40
Installation Instructions
4
Figure 2
Typical cabinet and floor planning dimension data, 47" (1194mm) cabinet 50-300kVA
Table 2
47-inch cabinet weight
Unit
kVA
Weight, lb (kg)
60 Hz
50 Hz
Without Transformer
50
1891 (858)
1966 (892)
1335 (606)
75
1995 (905)
2095 (950)
1335 (606)
100
2191 (994)
2316 (1051)
1335 (606)
125
2298 (1042)
2423 (1099)
1360 (617)
150
2490 (1129)
2640 (1198)
1360 (617)
200
2610 (1184)
2810 (1275)
1360 (617)
225
2800 (1270)
3000 (1361)
1390 (631)
300
2845(1290)
3045 (1381)
1390 (631)
Overall Dim.
39-1/2" (1003mm)
Including hinge
and bezel
projection
Overhead clearance
 of 18" (457mm)
recommended
for cooling airflow
Minimum side clearance
of 42" (1067mm) recommended
for service access if unit is
equipped with distribution
monitoring option
Shaded areas indicate
recommended clearance
of 42" (1067mm) at front and
rear for service access
For units with bottom
cable access, clearance
of 6" (152mm) below
unit is recommended
for cooling airflow
and cable entry/exit
Overall Dimension
48.6" (1235mm)
including side panels
78-1/2"
(1995mm)
47"
(1194mm)
36.4"
(925mm)
Unit Base Outline
Cabinet Dimensional Data
Shaded area indicates
cable access and
cooling airflow
Footprint and Floor
Cutout Dimensions
Front
1.3"
(33mm)
1.3"
(33mm)
33.8" (859mm)
35" (889mm)
6" (152mm)
6" (152mm)
Dia. location
3/4" (19mm)
typical
Floor Pedestals
available from
6" (152mm) to
18" (457mm)
9/16" (14mm)
diameter; 4 holes
typical
6" (152mm)
6" (152mm)
Unit Base Outline
Optional Floor Pedestals
36.4" (925mm)
1.5" (38mm)
2.3" (58mm)
Front
47" (1194mm)
43.8"
(1112mm)