Installation Instructions
6
Figure 3
Recommended minimum service and ventilation clearances
NOTE
1. Service access is required at the front and rear. 
2. Service access clearance dimensions: 36" (914mm) for units up to 150V to ground. 42" 
(1067mm) for units over 150V to ground.
3. Service access is required on the left side, if unit is equipped with Liebert Distribution 
Monitoring Option.
Table 3
Liebert FPC heat output
Unit kVA
 Full Load
Heat Output
BTU/Hr (kW)
15
2,500 (0.73)
30
4,600 (1.35)
50
6,200 (1.82)
75
8,150 (2.39)
100
9,900 (2.90)
125
11,500 (3.37)
150
12,500 (3.66)
200
15,500 (4.54)
225
15,800 (4.63)
300
18,450 (5.40)
Minimum clearance
 of 6" (152mm) below 
unit is recommended 
for cable entry and exit
Minimum clearance 
of 18" (457mm) 
above unit is 
recommended for 
cooling airflow
Front and rear access 
is required. See 
Notes 1 and 2.
See Notes 
and 3.