Emerson ITR Manuel D’Utilisation

Page de 74
Standard Features—All Systems
8
4.6.1 Condensate Pump
The condensate pump, mounted in the bottom of most units, is 
used for unit drain water only. The condensate pump is complete 
with sump, motor and pump assembly and automatic control.
The standard model has single float. A dual-float condensate 
pump, which includes connections to unit, common alarm, unit 
shutdown and one customer N/O contact is also available.
4.6.2 Remote Temperature/ Humidity Sensors
The remote temperature/ humidity sensors permit monitoring room conditions from an external 
source. They are encased in an attractive case and are provided with a plug compatible shielded cable 
in virtually any length.
4.6.3 Disconnect Switch—Locking Type
The locking disconnect switch, mounted in the electrical panel, is con-
nected to the safety lock dead front panel of the system and is inter-
locked mechanically. In this way the panel can’t be opened until the 
switch is in the off position. And it complies with local codes as well as 
those of the NEC.
Table 1
Condensate pump capacity
Voltage
Hz
Capacity
GPH (l/s)
Head Pressure
ft. (kPa)
200/230
50
50 (189)
10 (30)
208/230
60
50 (189)
17 (51)
380/415
50
200 (757)
26 (78)
460
60
200 (757)
43 (128)
Disconnect Switch
(Locking)