Emerson ITR Manuel D’Utilisation

Page de 74
System Data
32
Table 10
Liebert Challenger ITR glycol cooled data, 60 Hz
System Type
 BR = Horizontal Flow
 BM = Horizontal Flow with Econ-O-Coil
Glycol Cooled
GLYCOOL
Self-Contained
Split Systems
Self Contained
Indoor Unit
BR 071WG
BR 060E
BM 061G
Net Capacity Data
BTU/H
kW
BTU/H
kW
BTU/H
kW
100°F DB, 70°F WB (37.8°C DB, 21.1°C WB) 20% RH
Total
69,800
20.5
71,600
21.0
66,000
19.3
Sensible
69,800
20.5
71,600
21.0
66,000
19.3
Non Standard Flow Rates
1800 CFM, 21.5 GPM,
27.4 FT PD
2100 CFM
2600 CFM, 20.5 GPM,
24.6 FT PD
95°F DB, 68.3°F WB (35°C DB, 20.2°C WB) 24% RH
Total
68,600
20.1
72,300
21.2
64,700
19.0
Sensible
68,600
20.1
72,300
21.2
64,700
19.0
Non Standard Flow Rates
2100 CFM, 21.5 GPM,
27.4 FT PD
2600 CFM
2300 CFM, 19.5 GPM,
22.5 FT PD
90°F DB, 66.5°F WB (32°C DB, 19.2°C WB) 28% RH
Total
64,700
19.0
69,900
20.5
65,300
19.1
Sensible
64,700
19.0
69,900
20.5
65,300
19.1
Non Standard Flow Rates
2100CFM,18.5 GPM, 20.9FT PD
19.5 GPM, 22.5 FT PD
85°F DB, 64.4°F WB (29.4°C DB, 18°C WB) 32% RH
Total
62,800
18.4
66,200
19.4
61,500
18.0
Sensible
62,800
18.4
66,200
19.4
61,500
18.0
Non Standard Flow Rates
2300 CFM
80°F DB, 62.7°F WB (26.7°C DB, 17.1°C WB) 38% RH
Total
62,400
18.3
62,500
18.3
58,200
17.1
Sensible
62,400
18.3
62,500
18.3
58,200
17.1
80°F DB, 66.5°F WB (26.7°C DB, 19.2°C WB) 50% RH
Total
62,900
18.4
63,000
18.5
59,900
17.6
Sensible
53,200
15.6
53,200
15.6
51,200
15.0
75
°F
 DB, 62.5
°F
 WB (23.9
°C
 DB, 16.9
°C
 WB) 50% RH
Total
58,900
17.3
58,800
17.2
55,900
16.4
Sensible
51,500
15.1
51,500
15.1
49,500
14.5
75°F DB, 61.1°F WB (23.9°C DB, 16.2°C WB) 45% RH
Total
59,000
17.3
59,000
17.3
55,000
16.1
Sensible
59,000
17.3
59,000
17.3
55,000
16.1
72°F DB, 60.1°F WB (22.2°C DB, 15.6°C WB) 50% RH
Total
56,500
16.6
56,500
16.6
53,600
15.7
Sensible
50,500
14.8
50,500
14.8
48,500
14.2
72°F DB, 58.7°F WB (22.2°C DB, 14.8°C WB) 45% RH
Total
56,900
16.7
56,900
16.7
53,000
15.5
Sensible
56,900
16.7
56,900
16.7
53,000
15.5
GLYCOOL Coil Sensible Capacity
75°F DB, 62.5°F WB (23.9°C DB, 16.9°C WB) 45°F (7.2°C) EGT
47,700
14.0
Fan Data (Blower A12x9AT)** 
Standard Air, CFM (CMH)
2800 (4760)
2800 (4760)
2800 (4760)
Standard Fan Motor, hp (kW)
1-1/2 (1.1)
1-1/2 (1.1)
2 (1.5)
Opt Fan Motor, hp (kW)
2 (1.5)
2 (1.5)
N/A
Ext Static, in. WG (Pa)
.3 (75)
.3 (75)
.3 (75)
Evaporator Coil (V-Frame, at standard conditions)
Face Area, ft.
2
 (m
2
)
6.67 (.62)
6.67 (.62)
6.67 (.62)
Rows
4
4
4
Face Velocity, FPM (m/s)
405 (2.1)
405 (2.1)
405 (2.1)
Electric Reheat 2 Stage (Stainless Steel, Fin Tubular) - Standard
Capacity, inc. motor heat, BTU/H(element kW)
56,200 (15)
56,200 (15)
57,700 (15)
Hot Water Reheat 180°F (82.2°C) EWT, 75°F (23.9°C) EAT - Optional (includes standard air volume and optional fan motor hp)
Capacity, inc. motor heat, BTU/H(kW)
88,700 (26.0)
88,700 (26.0)
N/A
Flow Rate, GPM (l/s)
5.0 (.32)
5.0 (.32)
5.0 (.32)
Pressure drop, ft. (kPa)
16.9 (50.4)
16.9 (50.4)
16.9 (50.4)
Hot Gas Reheat - Optional (includes standard air volume and optional fan motor)
Capacity, inc. motor heat, BTU/H (kW)
54,900 (16.1)
54,900 (16.1)
N/A
*
The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the standard rating for 
ASHRAE 127-2001.All capacities are nominal values; actual performance will be ±5%. All above data is based on 40% ethylene glycol solution.
** Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for recommendations.