Emerson ITR Manuel D’Utilisation

Page de 74
System Data
34
Table 12
Liebert Challenger ITR glycol cooled data, 50 Hz
System Type
 BR = Horizontal Flow
 BM = Horizontal Flow with Econ-O-Coil
Glycol Cooled
GLYCOOL
Self-Contained
Split Systems
Self Contained
Indoor Unit
BR 070WG
BR 059E
BM 058G
Net Capacity Data
kW
BTU/H
kW
BTU/H
kW
BTU/H
37.8ºC DB, 21.1ºC WB (100ºF DB, 70ºF WB) 20% RH
Total
20.3
69,300
20.8
70,900
18.8
64,100
Sensible
20.3
69,300
20.8
70,900
18.8
64,100
Non Standard Flow Rates
1900 CFM, 24.5 GPM
2100 CFM
2000 CFM, 22.5 GPM
35ºC DB, 20.2ºC WB (95ºF DB, 68.3ºF WB) 24% RH
Total
19.6
66,800
20.7
70,800
17.8
60,600
Sensible
19.6
66,800
20.7
70,800
17.8
60,600
Non Standard Flow Rates
2000 CFM, 23.5 GPM
2500 CFM
2000 CFM, 20.5 GPM
32.2ºC DB, 19.2ºC WB (90ºF DB, 66.5ºF WB) 28% RH
Total
18.5
63,000
19.9
67,800
16.8
57,300
Sensible
18.5
63,000
19.9
67,800
16.8
57,300
Non Standard Flow Rates
2000 CFM, 21.5 GPM
2000 CFM
29.4ºC DB, 18ºC WB (85ºF DB, 64.4ºF WB) 32% RH
Total
17.9
61,200
18.8
64,200
16.9
57,700
Sensible
17.9
61,200
18.8
64,200
16.9
57,700
Non Standard Flow Rates
2200 CFM, 19.5 GPM
2400 CFM
26.7ºC DB, 17.1ºC WB (80ºF DB, 62.7ºF WB) 38% RH
Total
17.1
58,400
17.7
60,500
16.4
55,900
Sensible
17.1
58,400
17.7
60,500
16.4
55,900
Non Standard Flow Rates
2300 CFM
26.7ºC DB, 19.2ºC WB (80ºF DB, 66.5ºF WB) 50% RH
Total
17.2
58,800
18.0
61,400
16.8
57,400
Sensible
12.7
43,200
14.8
50,500
13.5
46,000
Non Standard Flow Rates
2000 CFM
2400 CFM
23.9ºC DB, 16.9ºC WB (75ºF DB, 62.5ºF WB) 50% RH
Total
16.7
57,000
16.8
57,200
15.9
54,100
Sensible
14.3
48,800
14.3
48,900
13.7
46,800
23.9ºC DB, 16.2ºC WB (75ºF DB, 61.1ºF WB) 45% RH
Total
16.7
56,900
16.3
55,800
15.4
52,700
Sensible
16.7
56,900
15.4
52,600
15.4
52,700
22.2ºC DB, 15.6ºC WB (72ºF DB, 60.1ºF WB) 50% RH
Total
16.0
54,600
16.1
54,800
15.2
51,800
Sensible
14.0
47,900
14.0
47,900
13.4
45,800
22.2ºC DB, 14.8ºC WB (72ºF DB, 58.7ºF WB) 45% RH
Total
16.1
54,800
16.1
55,000
14.9
50,700
Sensible
16.1
54,800
16.1
55,000
14.9
50,700
GLYCOOL Coil Sensible Capacity
23.9°C DB, 16.9°C WB (75°F DB, 62.5°C WB) 10°C (45°F) EGT
14
47,700.0
Fan Data (Blower A12x9AT)**
Standard Air, CMH (CFM)
4420 (2600)
4420 (2600)
4420 (2600)
Standard Fan Motor, kW (hp)
1.1 (1-1/2)
1.1 (1-1/2)
1.5 (2)
Optional Fan Motor, kW (hp)
1.5 (2)
1.5 (2)
N/A
Ext Static, Pa (in. WG)
75 (.3)
75 (.3)
75 (.3)
Evaporator Coil (V-Frame, at standard conditions)
Face Area, m
2
 (ft.
2
)
.62 (6.67)
.62 (6.67)
.62 (6.67)
Rows
4
4
4
Face Velocity, m/s (FPM)
1.9 (375)
1.9 (375)
1.9 (375)
Electric Reheat 2 Stage (Stainless Steel, Fin Tubular) - Standard
Capacity, element kW (inc. motor heat, BTU/H)
15 (56,200)
15 (56,200)
15 (56,200)
Hot Water Reheat 82.2°C (180°F) EWT, 23.9°C (75°F) EAT - Optional (Includes standard air volume and optional fan motor hp)
Capacity, inc. motor heat, kW (BTU/H)
25.3 (86,200)
25.3 (86,200)
25.3 (86,200)
Flow Rate, l/s (GPM)
.32 (5.0)
.32 (5.0)
.32 (5.0)
Pressure drop, kPa (ft.)
50.4 (16.9)
50.4 (16.9)
50.4 (16.9)
Hot Gas Reheat - Optional (Includes standard air volume and optional fan motor)
Capacity, kW (BTU/H) (includes motor heat)
15.0 (51,300)
15.0 (51,300)
15.0 (51,300)
*
The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the standard rating 
for ASHRAE 127-2001. All capacities are nominal values; actual performance will be ±5%. All data above is based on 40% ethylene glycol solution.
** Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for 
recommendations.